Data source points – Rockwell Automation FactoryTalk Historian SE 3.0 UniInt Interface User Guide User Manual

Page 82

Advertising
background image

UniInt Failover Scheme

76

Parameter

Value

Description

Host Historian Server
for Exceptions and
Historian tag updates

Computer:

IF-Node2

/Host=SecondaryPI

to send data to a Historian Server collective, the
value of the /host parameters should equal
different members of the collective.

This configuration will ensure output continue to
be sent to the Data Source if one of the
Historian Servers becomes unavailable for any
reason.

If the redundant interfaces are being configured
to send data to a Historian Server collective, the
value of the /host parameters should equal
different members of the collective.

This configuration will ensure outputs continue
to be sent to the Data Source if one of the
Historian Servers becomes unavailable for any
reason.

Data Source Points

The following table lists the points that are required on the Data Source with the values that
will be written to the points and comments describing the points.

Point

Value

Description

Active ID Point

Updated by the
redundant Interfaces

Can be changed
manually to initiate a
manual failover

Values range between 0
and the highest of the
Interface Failover IDs
(typically 2)

The Active ID Point on the datasource is used
by the interfaces to determine which interface is
currently sending data to Historian. This point
on the Data Source must be initialized so the
interfaces‟s first read of the value is not an
error.

The Active ID Point may be used to initiate a
manual failover. If the current value of the
Active ID point is 1, the value can be manually
changed to a 2 which will cause the interface of
IF-Node1 to transition to the backup role and
the interface of IF-Node1 to transition to the
primary role.

Heartbeat 1 Point

Updated by the Interface
on IF-Node1

Values range between 0
and 31

The Heartbeat 1 Point on the Data Source is
updated periodically by the interface on IF-
Node1. The interface on IF-Node2 monitors this
value to determine if the interface of IF-Node1
has become unresponsive.

Heartbeat 2 Point

Updated by the Interface
on IF-Node2

Values range between 0
and 31

The Heartbeat 2 Point on the Data Source is
updated periodically by the interface on IF-
Node2. The interface on IF-Node1 monitors this
value to determine if the interface of IF-Node2
has become unresponsive.