11

Chapter 1

Wire the Module

Connect the I/O, network and auxiliary cables to the module. The ArmorBlock EtherNet/IP family has 5-pin micro-style
connectors. Caps are provided to cover the unused connectors on your module. Connect the quick-disconnect cord sets
you selected for your module to the appropriate ports.

Functional Earth

This screw grounds the I/O block EtherNet/IP communication circuitry that is designed
to reduce the effect of noise on the network. The circuitry requires a solid earth-ground
connection, either through a metal screw to a grounded metal panel or through a wire.

I/O Connectors

Micro-style 5-pin Input Female Connector

Micro-style 5-pin Output Female Connector

Self-configuring Connector and Circuitry

D-code Micro Network Female Connector (EtherNet/IP)

LINK 1

MOD

NET

LINK 2

Functional Earth

1

2

5

4

3

2

1

3
4
5

Common

NC

NO

Ground

802B Limit Switch

(View into connector)
Pin 1

Sensor source voltage

Pin 2

Input B

Pin 3

Return

Pin 4

Input A

Pin 5

PE

2

1

A1

A2

3
4
5

Bulletin 100-K Contactor

(View into connector)
Pin 1

Not used

Pin 2

Output B

Pin 3

Return

Pin 4

Output A

Pin 5

PE

1

2

5

4

3

(View into connector)
Pin 1

Sensor source voltage

Pin 2

Input or output B

Pin 3

Return

Pin 4

Input or output A

Pin 5

PE

Output scan list

Input scan list

to PLC

from PLC

Input (or output) is on

Turn output on

Output

circuit

Input

circuit

Connector pin

Sensor or

actuator

1

2

5

4

3

4

2

3

1

5

(View into connector)
Pin 1

M12_Tx+

Pin 2

M12_Rx+

Pin 3

M12_Tx-

Pin 4

M12_Rx-

Pin 5

Connector shell shield FE

Advertising