FlexPak 3000 Field Current Regulator Installation Instructions

5.2

Setting Parameter 511 (FIELD ECONOMY REF)

For proper drive operation, the value for parameter 511 (

FIELD

ECONOMY

REF

) must be

set above the value for parameter 512 (

FIELD

LOSS

THRESHOLD

). Note that the default

value for

FIELD

ECONOMY

REF

is 0% and that the default value for

FIELD

LOSS

THRESHOLD

is 60% of

MOTOR

HOT

FLD

AMPS

. Using the defaults for parameters 511 and

512 will result in a drive fault.

See your drive’s manual for more information on setting the

FIELD

LOSS

THRESHOLD

parameter properly. Then complete the following steps.

If the drive is equipped with an OIM, complete steps 1-6. If the drive is equipped
with a DCM, skip to step 7.

Step 1. Select

FIELD

LOSS

THRESHOLD

by taking the following path form the main

menu:

Field
|____Field Current Regulator
|____Field Loop Configure

Step 2. Note the value of

FIELD

LOSS

THRESHOLD

.

Step 3. Back up to the Field Loop Configure menu and select

FIELD

ECONOMY

REF

.

Step 4. Set the value of

FIELD

ECONOMY

REF

to a value higher than that of

FIELD

LOSS

THRESHOLD

.

Step 5. Select MEMORY SAVE by taking the following path from the main menu:

Operator Interface
|____ Memory Operations

Step 6. Perform the Memory Save operation.

If the drive is equipped with a DCM, complete the following steps:

Step 7. From the main menu, scroll to Input Parameters and press ENTER.

Step 8. Scroll to

FIELD

LOSS

THRESHOLD

and note its value.

Step 9. Scroll to

FIELD

ECONOMY

REF

.

Step 10. Set the value of

FIELD

ECONOMY

REF

to a value higher than that of

FIELD

LOSS

THRESHOLD

.

Step 11. From the main menu, scroll to Memory Operations and press ENTER.

Step 12. Scroll to Memory Save, and then perform the memory save operation.

The installation procedure for the Field Current Regulator kit is now complete.

!

ATTENTION: Improper setting of the field economy ref parameter can
cause a motor overvoltage condition. Set the

MOTOR

HOT

FLD

AMPS

parameter to the motor’s nameplate value. Make sure the

FIELD

ECONOMY

REF

parameter and/or

FIELD

REF

parameter (P.513) are above the

FIELD

LOSS

THRESHOLD

parameter (P.512). Failure to observe this precaution

could result in bodily injury and damage to the equipment.