Field Current Regulator Description

A-5

Field Loss

When the Field Current Regulator is operating in fixed voltage mode, a field current
loss fault will be generated only when there is a complete loss of field current. When
the Field Current Regulator is regulating field current (that is, not in fixed voltage
mode), a field current loss fault will be generated when the field current drops below
the user-set

FIELD

LOSS

THRESHOLD

.

The same field feedback signal used by the Field Current Regulator is used by the
field loss detection circuit. The field current feedback will be compared against a
user-entered

FIELD

LOSS

THRESHOLD

. If the feedback is less than the threshold value, a

fault will be generated.

FIELD

LOSS

THRESHOLD

is entered as a percentage of

MOTOR

HOT

FLD

AMPS

(0-100% (speed regulator), 50-100% (armature voltage

regulator)).

FIELD

ECONOMY

REF

must be set above

FIELD

LOSS

THRESHOLD

to avoid field

loss faults when the drive enters field economy.

A field loss fault will also occur if the digital value on the A/D converter reaches full
scale (approximately 28% above the rated field output).

The Regulator board hardware jumper, J20

FIELD

LOSS

DETECT

, is designed to allow

the user to separately excite the motor field winding, and is not intended as a means
of bypassing field loss detection when using an internal field supply. Therefore, when
the Field Current Regulator kit is installed, this jumper is ignored. Note that leaving
J20 in the DISABLE position will NOT disable field loss detection.

Field Economy

The output parameter

FIELD

ECONOMY

ACTIVE

indicates when field economy is active.

Field economy becomes active after a user-defined time delay (

FIELD

ECONOMY

DELAY

)

from the time the motor stops or the drive is powered up. When the Field Current
Regulator is operating in fixed voltage mode, a constant field voltage is generated,
regardless of the state of

FIELD

ECONOMY

ACTIVE

.

The Field Current Regulator will provide field economy with a user-adjustable field
current reference (

FIELD

ECONOMY

REF

). This parameter is entered as a percentage of

MOTOR

HOT

FLD

AMPS

.

FIELD

ECONOMY

REF

must be set above

FIELD

LOSS

THRESHOLD

to

avoid nuisance field loss faults.

Overspeed Protection

Overspeed detection is active only when a tachometer is being used (

FEEDBACK

SELECT

ARMATURE

VOLT

). Because of this, the amount of field weakening is limited

when the drive is configured as a voltage regulator (

FEEDBACK

SELECT

=

ARMATURE

VOLT

).

Overvoltage Protection

Armature overvoltage protection is always active, regardless of the type of feedback.
This will reduce the chance of overvoltaging the armature due to a weakened field. An
overvoltage fault will occur when the armature terminal voltage exceeds 130 percent
of

MOTOR

RATED

ARM

VOLTS

.