Field Current Regulator Description

A-1

A

PPENDIX

A

Field Current Regulator Description

Description of the Field Control Loop

The FlexPak 3000 version 3 regulator will detect the presence of the Field Current
Regulator kit at power-up. The output parameter

FLD

CURRENT

REGULATOR

indicates

whether or not the Field Current Regulator kit is in-stalled. When the Field Current
Regulator kit is installed, the field current control loop operates and drive parameters

ENHANCED

FLD

VOLT

ADJ

and J21

FLD

SUPPLY

JUMPER

are ignored. The regulated field

loss and field economy circuits become active in place of those used by the standard
and enhanced field supplies. See figure A.1 for a block diagram of the field control
loop.

Important: The regulator board jumper J20 (

FIELD

LOSS

DETECT

) is ignored when the

Field Current Regulator is in-stalled. Therefore, setting J20 to the
DISABLE position will NOT disable field loss detection.

The field control loop contains two regulators: a field current regulator and an
armature voltage (counter-EMF or CEMF) regulator. The field control loop can be
configured to decrease armature voltage when the armature voltage feedback
(

ARMATURE

VOLTAGE

) exceeds the

FLD

WEAKEN

THRESHOLD

voltage and the field begins

to weaken (see figures A.1 and A.2). The armature IR drop can be compensated for
by using the

IR

COMPENSATION

parameter (P.206).

The output of the Field Current Regulator determines the firing angle of the regulated
field supply gate firing circuit. The output parameter

FIELD

DELTA

represents the angle

in degrees. If the factory defaults for the Field Current Regulator are in effect, it will
operate in a fixed voltage mode by firing the field SCRs at a fixed angle of 117º. This
will produce a field voltage of 150 VDC at 230 VAC line input or 300 VDC at 460 VAC
line input. For other motor field voltages,

MOTOR

HOT

FLD

AMPS

must be set properly

before the motor field is connected. While the Field Current Regulator is producing
fixed voltage, the value for

MOTOR

HOT

FLD

AMPS

will be set to 0.01 amps. After a valid

value is entered for

MOTOR

HOT

FLD

AMPS

, the user-assigned value for

FIELD

LOSS

THRESHOLD

becomes effective. The Field Current Regulator will NOT regulate field

current until a valid value for

MOTOR

HOT

FLD

AMPS

is entered. While in fixed voltage

mode, a field loss fault will only occur if there is a complete loss of field current. This is
similar to having a standard or enhanced field supply installed.

!

ATTENTION:If the factory defaults for the Field Current Regulator are
not in effect (e.g.,

MOTOR

HOT

FLD

AMPS

was modified via the network or

CS3000), extreme care must be exercised to ensure the correct value
for

MOTOR

HOT

FLD

AMPS

is present when power is applied to the drive.

Failure to observe this precaution could result in damage to, or
destruction of, the equipment.