The speed of sound changes roughly 1% per 6° C (10° F). QT50U series ultrasonic sensors have temperature

compensation available, via the 8-pin DIP switch. Temperature compensation will reduce the error due to temperature by

about 90%.

NOTE: If the sensor is measuring across a temperature gradient, the compensation will be less

effective.

Configuration

3

ON

DIP

Figure 1. Removing the Access Cover

1 2 3 4 5 6 7 8

ON

DIP

1 2 3 4 5 6 7 8

ON

DIP

ON Position

Figure 2. DIP Switch Location

The QT50U features an 8-pin DIP switch

bank for user setup. The DIP switches are

located behind the access cover on the back

of the sensor as shown. A spanner tool is

included with each sensor for removing the

cover.

Switch

Function

Settings

1

PNP or NPN Select

ON = Both outputs set for PNP

OFF* = Both outputs set for NPN

2

Window/Fill Level

ON = High/Low (fill level control)

OFF* = ON/OFF (window)

3

Output Operation

Window selected on Switch 2:

ON* = Normally open

OFF = Normally closed

Fill Level selected on Switch 2:

ON = Pump-in

OFF = Pump-out

4

Teach/Disable Control

ON* = Configured for remote teach

OFF = Configured for transmit disable

5 and 6

Response (100 ms/cycle)

1 cycle

4 cycles*

8 cycles

16 cycles

Switch 5

OFF

ON*

OFF

ON

Switch 6

OFF

OFF*

ON

ON

7

Temperature Compensation

ON* = Enabled

OFF = Disabled

8

Factory Calibration

ON = For factory calibration only; switch should be set to OFF for use

OFF* = DIP-switch settings in control

* Factory default settings

DIP Switch Selectable Functions

CAUTION: To avoid damage to the sensor caused by static discharge (ESD), observe proper ESD

precautions (grounding) while adjusting the DIP switches.

Switch 1: Output Mode Select

ON = Both outputs set to PNP (current sourcing)
OFF = Both outputs set to NPN (current sinking)

This switch configures the sensor internally to use either the PNP or NPN output configuration.

Switch 2: High/Low Level Control

ON = High/Low (fill level control)

U-GAGE QT50UDB Series Sensors with Dual-Discrete Outputs

2

www.bannerengineering.com - tel: 763-544-3164

P/N 110112 Rev. B