System installation, Warning, 5 electrical connections – Banner EZ-SCREEN­ Safety Light Curtain Systems User Manual

Page 29

Advertising
background image

P/N 68413 rev. A

27

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

EZ-SCREEN Point

Instruction Manual

System Installation

Installations With Corner Mirrors

If corner mirrors are used in the application, measure and 

position them as for the sensors . Refer to the data sheet packed

with the mirrors for specific installation instructions.  
1.  Follow emitter/receiver installation steps 1-3 for installation 

without mirrors.

2.  Mount the mirror(s) at the desired locations, parallel to the 

emitter and receiver. (Use a level to verify plumb, if the floor 

surface is level.) Measure up from the floor to position the 

center of the mirror’s reflective surface at the vertical center 

of the beam grid, using the beam location marks on the 

emitter as a guide. Allow additional reflective area above the 

top beam and below the bottom beam. Angle the mirror(s) 

relative to the sensors, so that one sensor’s front surface can 

be seen in the first mirror when standing directly in front of 

the other sensor, looking into the mirror.

Installations with ACCESS-GUARD Kit

1 . Install the supplied Banner MSA series stands and bases per

the instructions supplied with the MSA series stands.

2.  Mount the Emitter and Receiver on one stand (using the 

supplied mounting brackets) and mount the supplied SSM-

100 mirrors (using the supplied 45° brackets) on the other 

stand .

3.  Check the floor for level. If the floor is level, check both 

stands for plumb. Use the base adjusting bolts, if needed, and 

tighten the base mounting bolts .

4.  Position the emitter, receiver and mirrors so that the beam 

path meets the requirements of the applicable standards . See

Mounting the Sensors and Figure 3-13 on page 29.

Mounting the Reset Switches

Mount all external Reset switches outside the guarded area, 

and out of reach from within the guarded area. The entire 

safeguarded area should be visible from the Reset switch 

locations. If any areas are not visible, other means must be 

used to ensure that no personnel are within the safeguarded 

area during the reset (see Warning).
Reset switches must be protected from accidental or 

unauthorized operation (e.g., through the use of a key, guards, 

or rings).

WARNING . . .

Reset Switch Location

Reset switch(es) must be:
•  Outside of the hazardous area, in a location that allows the switch 

operator full view of the entire guarded area,

•  Out of reach from within the safeguarded space, and
•  Protected against unauthorized or inadvertent operation.
If any areas are not visible from the Reset switch(es), additional 
means of safeguarding must be provided, as described by the ANSI 
B11 series or other appropriate standards .
Failure to do so could result in serious injury or death. 

3.5 Electrical Connections

Make the electrical connections in the order described in this

section. It is the user’s responsibility to maintain factory-rated 

sealing at all cable access ports in the wiring chamber end cap 

of each sensor. One or more of the access ports may be used; 

proper wiring entrance hardware (conduit or cable gland) must 

be used in each opened access port in order to maintain the

NEMA 4, 13; IEC IP65 rating.
NOTE:  EZ-SCREEN wiring is low voltage; running these wires 

alongside power wires, motor/servo wires, or other high-

voltage wiring, can inject noise into the EZ-SCREEN 

System. It is good wiring practice (and may be required 

by code) to isolate EZ-SCREEN System wires from high-

voltage wires.

Wiring barriers in the wiring chamber end caps can accept 

individual conductors from #22 to #16 AWG or two conductors 

from #22 to #18 AWG. The wires used should have an insulation 

temperature rating of at least 90°C (194°F).

WARNING . . .

Proper Electrical

Hookup

•  Electrical hookup must be made by Qualified Personnel

and must comply with NEC (National Electrical Code) and local 
standards .

•  Make no connections to the System other than those

described in Section 3.5 of this manual. Doing so could result
in serious injury or death.

WARNING . . .

ACCESS-GUARD

Configuration

The ACCESS-GUARD must be properly installed,

e.g. at a beam spacing of 500 mm the range can not exceed 8 
meters, to prevent the possibility of misalignment creating voids in 
the sensing area or false proxing. See Figure 3-3.