EZ-SCREEN Point

Instruction Manual

System Installation

2-Channel (Dual-Channel) Control

Two-channel control provides the ability to electrically extend 

the safe switching point beyond the FSD contacts. With proper 

monitoring (i.e. EDM), this method of interfacing is capable 

of detecting certain failures in the control wiring between the 

safety stop circuit and the MPCEs. These failures include a 

short-circuit of one channel to a secondary source of energy or 

voltage, or the loss of the switching ability of one of the FSD 

outputs. Such failures could lead to the loss of redundancy — or 

to a complete loss of safety, if not detected and corrected. 
The possibility of a failure to the wiring increases as the physical 

distance between the FSD safety stop circuits and the MPCEs 

increase, as the length or the routing of the interconnecting 

wires increases, or if the FSD safety stop circuits and the 

MPCEs are located in different enclosures. For this reason, 

2-channel control with EDM monitoring should be used in any 

installation where the FSDs are located remotely from the 

MPCEs. 

1-Channel (Single-Channel) Control

One-channel control, as mentioned, uses a series connection of 

FSD contacts to form a safe switching point. After this point in 

the machine’s safety-related control system, failures can occur 

that would result in the loss of the safety function (such as a 

short-circuit to a secondary source of energy or voltage). 
For this reason, 1-channel control interfacing should be used 

only in installations where FSD safety stop circuits and the 

MPCEs are mounted within the same control panel, adjacent to 

each other, and are directly connected to each other; or where 

the possibility of such a failure can be excluded. If this can not 

be achieved, then 2-channel control should be used. 
Methods to exclude the possibility of these failures include, but 

are not limited to:

•   Physically separating interconnecting control wires from each 

other and from secondary sources of power.

•   Routing interconnecting control wires in separate conduit, 

runs, or channels.

•   Locating all elements (modules, switches, and devices under 

control) within one control panel, adjacent to each other, and 

directly connected with short wires.

•   Properly installing multi-conductor cabling and multiple wires 

through strain-relief fittings. (Over-tightening of a strain-relief 

can cause short-circuits at that point.)

•   Using positive-opening or direct-drive components, installed 

and mounted in a positive mode.