Units

Description

Definition

2

0 to 20 mA

Default analog input unit. Modbus register contents are scaled such that 0 represents 0 mA and 65535
represents 20 mA.

LCD: 0.00mA–20.00mA

3

Discrete (ON/
OFF)

Default discrete unit.

LCD: ON/OFF

4

0 to 10 V
(Volts)

Analog unit using 0 to 10 V instead of current. Modbus register contents are scaled such that 0 represents
0 V and 65535 represents 10 V.

LCD: 0.00V–10.00V

5

Signed Analog,
0 to 10 V

For a signed value, such as temperature, that is to be converted to a voltage out value. Use null to set the
start point and span to define the range. The null value is the starting temperature to be associated with 0
V. The span is the entire temperature range that is to be associated with 0 to 10 V.

LCD: 0.00V–10.00V

6

Signed Analog,
0 to 20 mA

For a signed value, such as temperature, that is to be converted to a mA out value. Use null to set the
start point and span to define the range. The null value is the starting temperature to be associated with 0
mA. The span is the entire temperature range that is to be associated with 0 to 20 mA.

LCD: 0.00mA–20.00mA

7

Unsigned
Analog, 0 to 20
mA

For unsigned values, such as a counter, that is to be converted to a mA out value. Use the null to set the
start point and span to define the range. The null value is the distance to be associated with 0 mA. The
span is the entire distance range that is to be associated with 0 to 20 mA.

LCD: 0.00mA–20.00mA

8

Signed Analog,
4 to 20 mA (A)

In older models, this units type is for degree Celsius conversions only. Use null to set the start point and
span to define the range. The null value is the starting temperature to be associated with 4 mA. The span
is the entire temperature range that is to be associated with 4 to 20 mA. For newer firmware models, type
codes 8 and 9 are treated the same.

LCD: 4.00mA–20.00mA

9

Signed Analog,
4 to 20 mA (B)

In older models, this units type is for degree Fahrenheit conversions only. Use null to set the start point
and span to define the range. The null value is the starting temperature to be associated with 4 mA. The
span is the entire temperature range that is to be associated with 4 to 20 mA. For newer firmware models,
type codes 8 and 9 are treated the same.

LCD: 4.00mA–20.00mA

10

Unsigned
Analog, 0 to 10
V

For an unsigned value, such as 0 to 20 mA, that is to be converted to a voltage out value. Use the null to
set the start point and span to define the range. The null value is the distance to be associated with 0V.
The span is the entire distance range that is to be associated with 0 to 10 V.

LCD: 0.00V–10.00V

11

Counter, 16-bit

The 16-bit counter value records counts up to 65535.

LCD: 0000

12

Unsigned
Analog, 4 to 20
mA

For an unsigned value, such as 0 to 10 V, that is to be converted to a mA out value. Use the null to set
the start point and span to define the range. The null value is the distance to be associated with 4 mA.
The span is the entire distance range that is to be associated with 4 to 20 mA.

LCD: 4.00mA–20.00mA

SureCross Wireless I/O Networks