Modbus register 8 device messages are disabled. The Modbus register 8 clears or disables

messages using the Gateway’s Modbus register 15. (Decimal values 65024 through 65279.)

10.4 Inputs and Outputs

Some inputs or outputs are not working.

Option 1. From the Node, access the menu system and use manual scrolling mode within *RUN to freeze the I/O status on

the LCD display for the device in question. Verify that when the input device changes state or changes value, the LCD

mirrors the behavior. If the Node is in a hazardous location, access the Node's I/O from the Gateway by changing the

Gateway's right rotary dial to the Node number in question. For example, to view the I/O status of Node 3, move the

Gateway's right rotary dial to 3. The Gateway's LCD now scrolls through Node 3's I/O. To freeze the display on a particular

I/O point, double-click button 2. The autoscrolling on the Gateway stops at the *RUN screen. Single-click button 1 to

advance through the Node's I/O points.

Option 2. Verify the LCD on the output side mirrors the linked input’s behavior. If the input device state LCD on the

origination DX80 and the LCD on the destination DX80 behave the same, there may be a wiring issue or an interfacing

problem. Consult the factory.

Option 3. Nodes will not sample inputs unless the Nodes are in sync with a Gateway. Verify your Node is in sync with its

Gateway.

10.5 Radio Link Time-Out and Recovery (Non-Host Connected Systems)

The SureCross

®

wireless devices employ a deterministic link time-out method to address RF link interruption or failure. As

soon as a specific Node/Gateway RF link fails, all pertinent wired outputs are de-energized until the link is recovered (see

component data sheet for more information.) Through this process, users of Banner wireless networks can be assured that

disruptions in the communications link result in predictable system behavior.

The link time-out feature uses a fully-acknowledged polling method to determine the RF link status of each Node on the

network.

If after a specified number of sequential polling cycles the Node does not acknowledge a message, the Gateway considers

the link with that Node timed out. LCD displays on both the Node and Gateway show *ERROR. Following a time-out, the

Node de-energizes outputs and the Gateway sets all outputs linked to the Node in question to a de-energized state. Inputs

from the Node mapped to outputs on the Gateway are suspended during a link time-out.

Gateway

Node 1

Node 2

OUT 1 = 0
OUT 2 = 0

OUT 1 = Normal
OUT 2 = Normal

OUT 1 = 0
OUT 2 = 0

OUT 3 = Normal
OUT 4 = Normal

Figure 3. Radio link between the Gateway and Node 1 has timed out.

After a link has failed, the Gateway must receive a specified number of good RF communications packets from the Node in

question before the link is reinstated. Outputs are restored to current values when the link is recovered.