Definition/Solution

Flashing red

Gateway, DX85: Modbus communication error

For a Gateway system, a Modbus communications error indicates a bad

transmission or checksum error between the host and the Gateway device. For a

GatewayPro system, a Modbus communications error indicates a communications

problem internal to the GatewayPro. For a Gateway and Ethernet Bridge system, a

Modbus communication error indicates a communication problem between the

Gateway and the Ethernet Bridge.

Solutions:

1. The default communications settings for the RS485 port are: 1 start bit, 8

data bits, no parity, 1 stop bit, and 19.2k baud. The DX80 Gateway uses

Modbus RTU protocol for all communications. Supported Modbus function

codes are 3, 6, and 16.

2. Verify the DX80 model supports RS485 serial communications.
3. RS485 termination or biasing is not supplied on the Gateway and should

be provided externally to the DX80. (Termination is not required by the

Gateway, proper biasing of the serial lines is required.)

4. Bad connection or bad cable.

Flashing red

Node: No radio communication

There are two settings on every Node device used to synchronize to the Gateway

device:

The Node must be bound to the Gateway.

Each Node ID within that network must be set to a unique number.

Solutions:

1. If the Gateway and Node are less than two meters apart, device

communication may fail (radios may saturate). If the Gateway is less

than two meters from another Gateway, send and receive transmissions

between all devices the Gateways communicate with fails.

2. The Gateway and Node may be too far apart to achieve synchronization –

consult the factory for options.

3. Use a qualified antenna on both the Gateway and Node devices.
4. After any system parameter change, cycle the power to re-synchronize all

devices.

5. When a Node loses synchronization, it is programmed to attempt re-

synchronization for five seconds, then sleep for fifteen seconds.

Synchronizing may require up to twenty seconds.

6. Re-cycle power on the Gateway and Node devices.

Not blinking amber

GatewayPro: No Modbus communication

Solution:

1. The GatewayPro’s LED 2 should always be blinking amber to indicate

Modbus communication. If the LED 2 does not blink amber, verify the

baud rates, slave IDs, parity, and stop bits are set correctly.

2. Check the cables connecting the GatewayPro to the host device.

No LED 1

No LED 2

All DX80 devices display “POWER” on the LCD for the first five to ten seconds

after applying power. A DX80 Gateway always has a green LED 1 on when power

is connected. DX80 Node devices flash a red LED 2 every three seconds or a

green LED 1 every second depending on the RF Link status.

If no LEDs are lighting up:

1. Put battery powered devices into power-down mode by pressing and

holding button 1 for three to five seconds. To return from power-down

mode, press and hold button 1 for three to five seconds.

2. Recheck the power connections and power requirements. Battery-

powered devices require 3.6–5.5V dc. Non-battery powered devices

require 10–30V dc.

3. After replacing the battery, allow up to sixty seconds for the device to

power up.

4. The GatewayPro cannot be attached to another Modbus master device or

a Modbus slave ID 1 via RS-485. Special configuration using the Web

page configuration tool allows the GatewayPro to become a slave unit

when necessary.