7.1.3 Discrete Inputs, MINI-BEAM

MINI-BEAM

Discrete IN

SP1

MINI-BEAM

Two-wire MINI-BEAM sensor using a FlexPower Node and

powered using the Node’s switch power.

7.2 Discrete Outputs

7.2.1 Discrete Outputs

Sourcing (PNP)

Sinking (NPN)

Discrete OUT

GND

PWR

10-30V dc

Load

dc common

Load

Discrete OUT

GND

PWR

10-30V dc

dc common

Wiring diagram for a sourcing (PNP) two-wire output load

powered using the SureCross device terminal block. Under

certain conditions, the dc commons between the load and

the SureCross device might need to be connected.

Wiring diagram for a sinking (NPN) two-wire output. Under

certain conditions, the dc commons between the load and

the SureCross device might need to be connected.

The sensor's power source might need to be the same as

the SureCross device power source.

7.3 Analog Inputs

Analog Sensors. For analog sensors, the ground/dc common of the sensor should be connected to the ground of the

DX80 device. For best results, Banner recommends that the power source for the sensor and DX80 device is the same.

7.3.1 Analog Inputs, Powered using SureCross Device Terminals

Two-Wire Sensors

Three-Wire Sensors

Analog IN

PWR

10-30V dc

GND

+

sensor

dc common

Analog IN

PWR

10-30V dc

GND

+

sensor

dc common

Two-wire analog sensor powered from a 10–30V dc power

SureCross device using the PWR terminal.

Do not exceed analog input ratings for analog inputs. Only

connect sensor outputs to analog inputs.

Three-wire analog sensor powered from 10–30V dc power

SureCross device using the PWR terminal.

Do not exceed analog input ratings for analog inputs. Only

connect sensor outputs to analog inputs.