1. Housing. The rugged, industrial DX80 housing meets IEC
IP67 standards.
2. Mounting hold, #10/M5 clearance. Mounting Holes accept
metric M5 or UNC/UNF #10 hardware -- DIN rail mount
adapter bracket available.
3. Wiring terminal strip. The 16 spring-clip type wiring
terminals accept wire sizes: AWG 12-28 or 2.5 sq mm.
4. Port, PG-7 gland or blank. The PG-7 threaded ports can
accept provided cable glands or blanks.
5. Ribbon connector. Ribbon cable connects wiring base to
LCD/radio.
The GatewayPro has no serviceable parts inside the housing and no wiring chamber. During setup or standard operation,
there should not be a need to open the GatewayPro.
2.3 DX80 GatewayPro
The GatewayPro has many of the same features as the Gateway and Node, including the LEDs, the buttons, LCD, and
Euro-style connector.
1
2
3
4
5
6
7
1. Industrial ethernet port, female.
2. Rotary switch 1 (left). Sets the Network ID (NID) to a hexidecimal
value from 0 to F, for a total of 16 Network IDs. A Gateway and its
corresponding Nodes must be assigned the same Network ID.
3. Rotary switch 2 (right). On the Gateway, sets the Gateway’s LCD
viewing device address. The Gateway is predefined as Device Address 0.
On the Node, sets the Node’s Device Address (hexidecimal 1 to F). Each
Node within a network must have a unique Node Device Address.
3. Push button 1. Single-click to advance across all top-level DX80
menus. Single-click to move down interactive menus, once a top-level
menu is chosen.
4. Push button 2. Double-click to select a menu and to enter manual
scrolling mode. Double-click to move up one level at a time.
5. LED 1 and 2. Provide real-time feedback to the user regarding RF link
status, serial communications activity, and the error state.
6. LCD Display. Six-character display provides run mode user
information and shows enabled I/O point status. This display allows the
user to conduct a Site Survey (RSSI) and modify other DX80
configuration parameters without the use of a PC or other external
software interfaces. On the Node, after 15 minutes of inactivity, the LCD
goes blank. Press any button to refresh the display.
7. 5-pin M12 Euro-style quick disconnect serial port.
2.4 DX83 Ethernet Bridge
The DX83 Ethernet Bridge uses the same housing and same mounting holes as the Gateway and Node.
SureCross Wireless I/O Networks
9