Sensor programming, Status indicators – Banner T-GAGE M18T Series Temperature Sensors User Manual

Page 3

Advertising
background image

Apparent Temperature

Two factors that have a large influence on apparent temperature are the object’s emissivity and whether or not the object fills the sensor’s
field of view.

Object Emissivity:

A “blackbody” is a “perfect” emitter, with an emissivity of 1.0 at all temperatures and wavelengths. Most surfaces emit only a
fraction of the amount of thermal energy that a blackbody would. Typical T-GAGE applications will be sensing objects with
emissivities ranging from 0.5 to 0.95. Many references are available with tables of emissivity coefficients for common materi-
als. In general, shiny unpainted metals have low emissivity, while non-glossy surfaces have high emissivity.
Shiny surfaces: a mirror or shiny surface can redirect an object’s emitted energy to an undesired location, or even bring
additional unintended thermal energy into the sensor’s field of view (see

Application Note

on page 6).

Object Size:

If the object being detected does not fill the sensor’s field of view, then the sensor will average the temperature of that object
and whatever else is in the sensing field of view. For the sensor to collect the maximum amount of energy, the object should
completely fill the sensor’s field of view. However, in some applications, when the object is too small, this may not be possi-
ble. In such cases, if the object is hot enough, the thermal contrast may still be adequate to trigger the sensor’s output.

Sensor Programming

Two TEACH methods may be used to program the sensor:

• Teach individual minimum and maximum limits (Two-Point Static Teach), or
• Dynamic Teach for on-the-fly programming.

The sensor may be programmed either via its push button, or via a remote switch. Remote programming also may be used to disable the
push button, preventing unauthorized personnel from adjusting the programming settings. To access this feature, connect a normally
open switch between the sensor’s gray wire and dc common or connect the gray wire to a digital input (PLC).

NOTE: The impedance of the Remote Teach input is 3 kΩ.

Programming is accomplished by following the sequence of input pulses (see

Teaching Limits Using Two-Point Static TEACH

on page

4). The duration of each pulse (corresponding to a push button “click”), and the period between multiple pulses, are defined as “T”:

0.04 seconds < T < 0.8 seconds

Status Indicators

Power ON/
OFF LED

Indicates

OFF

Power is OFF

ON Green

Sensor is in Run mode

ON Red

TEACH is active

Output LED

Indicates

OFF

Run Mode: Output is OFF

TEACH Mode: Waiting for Output OFF condition

ON Yellow

Run Mode: Output is energized

TEACH Mode: Waiting for Output ON condition

Flashing Yellow

Dynamic TEACH active

M18T T-Gage Sensor

P/N 120632 Rev. A

www.bannerengineering.com - tel: 763-544-3164

3

Advertising
This manual is related to the following products: