Teaching Limits Using Two-Point Static TEACH

Two-Point TEACH is the traditional setup method, used when two conditions can be presented individually by the user. The sensor es-
tablishes a single sensing threshold (the switchpoint) midway between the two taught conditions, with the Output ON condition on one
side and the Output OFF condition on the other.
General Notes on Programming

• The sensor will return to RUN mode if the first TEACH condition is not registered within 60 seconds
• After the first limit is taught, the sensor will remain in PROGRAM mode until the TEACH sequence is finished

Switching

Hysteresis

OFF

Threshold

Cold

Limit

Hot

Limit

0° C

300° C

2nd taught

(Output OFF)

Condition

1st taught

(Output ON)

Condition

ON Threshold

(Set at midpoint of

taught conditions)

When object to be sensed is hotter than ambient

Switching

Hysteresis

OFF

Threshold

Cold

Limit

Hot

Limit

0° C

300° C

1st Taught

(Output ON)

Condition

2nd Taught

(Output OFF)

Condition

ON Threshold

(Set at midpoint of

taught conditions)

When object to be sensed is colder than ambient


Figure 3. Two-Point Static Teach

Two-Point TEACH Procedure

Result

Push Button

Remote Line

(0.04 sec < T < 0.8 sec)

Programming

Mode

• Push and hold

push button for 2
seconds

No action required

• Power LED turns Red
• Output LED turns Yellow

Learn Output

ON Condition

• Present Output ON

condition

• "Click" the push

button

• Present Output ON condition
• Single-pulse the remote line

T

• Output LED turns OFF

Learn Output

OFF Condition

• Present Output

OFF condition

• "Click" the push

button

• Present Output OFF condition
• Single-pulse the remote line

T

Teach Accepted

• Power LED turns Green
• Sensor automatically sets the switch-

ing threshold and returns to Run
mode

Teach Unacceptable
Sensor returns to beginning of Teach

Exit Without

Save

• Push and hold

push button for 2
seconds

• Hold remote line low for 2 sec-

onds

2 seconds

Sensor returns to Run mode without sav-
ing new settings