background image

LED

Fault, Probably Cause, and Procedures

Fault ON
Input 1 ON or OFF
Input 2 ON or OFF
Output OFF

a. 2-channel simultaneity > 3 seconds (configured for 2-channel
operation)
b. Channel simultaneity > 1 second (NO/NC did not switch within 1
second)
See

Configuration

on page 3 for description of complementary

switching and 2-channel operation.

Power FLASHING
Fault FLASHING
Input 1 OFF
Input 2 OFF
Output OFF

DIP-SWITCH ERROR
a. DIP-switch settings are incorrect; Bank A does not match Bank
B
See

Configuration

on page 10 for DIP-switch configuration.

Power ON
Fault ON
Input 1 ON
Input 2 ON
Output FLASHING

OPEN RESET FAULT
a. Y1/Y2 open when configured for Auto Reset
See

Configuration

on page 10 for Manual/Auto Reset information.

Power ON

Fault FLASHING

Input 1 OFF

Input 2 OFF

Output OFF

INTERNAL FAULT (See

Repairs

on page 19)

a. Incorrect check sum
b. Internal relay failure (e.g., welded contact due to inductive load
arcing.)
c. Low input power
d. Other internal fault

EC Declaration of Conformity

Banner Engineering Corp.

9714 Tenth Avenue North

Minneapolis, MN 55441-5019 USA

We herewith declare that GM-FA-10J Gate Monitoring Safety Module for industrial control is in conformity with the provisions of the Ma-
chinery Directive (Directive 98/37/EEC), and all essential Health and Safety Requirements have been met.

R. Eagle / Engineering Manager

10/16/2009

Download the complete EC Declaration of Conformity as a PDF file at

www.bannerengineering.com/ESMODULE

Banner Engineering Corp Limited Warranty

Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of
shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned
to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse,
abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (IN-
CLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND
WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.

GM-FA-10J Gate Monitoring Safety Module

P/N 060998 Rev. F

www.bannerengineering.com - tel: 763-544-3164

21

Advertising