Pak 200i – Tweco PAK 200i User Manual

Page 121

Advertising
background image

PAK 200i

Manual 0-5335

APPENDIX

A-41

System Bias supply PCB is powered from the 3 phase AC input and works from about 150V to over 600V covering

all the normal voltage ranges. It can operate from 2 phases (single phase) so it still provides bias power and can

Art # 12299

report a fault if a phase is missing. The supply’s output is 24 VDC which powers the Relay board, the Display, the

Pilot board and the � boards in the CCM. System Bias also contains circuits to detect missing phase and determine

if the AC voltage is within the correct range, not too high or too low. It also signals to the CCM what voltage the

unit is configured for. The System Bias supply PCB includes a relay, K1, which only applies voltage to Auxiliary

transformer, T1, primary when the input voltage is in the correct range.

The

Relay and Interface PCB Accepts and distributed the output of the Aux Transformer. It has relay to control

the pump, fans, input contactors, the Arc Starter and the Inrush relays. A circuit on the Relay board accepts input

from the Work current sensor, HCT1, and Pilot current sensor (on the Pilot PCB) and sends the Enable signal to

the Pilot boards IGBT switches via the J3 to J42 ribbon cable. Other inputs on the Relay board include those from

the Negative Temperature Coefficient (NTC) ambient and coolant temperature sensors. Coolant tank level switch

and coolant flow switch, which determines if the flow is above the required minimum rate, also send signals to the

Relay Board. Ultra-Cut units include a flow sensor whose output to the Relay Board is a series of pulses whose

frequency indicates the flow rate and can detect the presence of

gas bubbles in the coolant. All these signals pass to the CCM

via a 40 conductor ribbon cable going to the CCM I/O board.

The

Display Board Has LEDs for AC, TEMP, GAS & DC. It

also has a 4 digit 7 segment display for status and fault infor-

mation. AC LED indicates the input contactors to the inverters

have been commanded to close, but does not mean they are

closed. TEMP means one or more inverters or the coolant has

exceeded the allowed temperature. GAS means gas is flowing

and coolant flow is OK. DC means the inverters output voltage

is above 60 VDC.

The first digit of the 7 segment display shows the letter, “C”;

“E”; “L” or is blank. During the initial power up sequence the

letter “C” followed by the other 3 digits, indicates the CCM

code revision. Status or Fault codes which may occur during

the power up sequence or any time thereafter are preceded by

letters “E” for an active fault or “L” for a “latched” or “last”

fault that stopped the process but is no longer active. When

there is no Fault or active Status code, the output current set-

ting is displayed with the first digit blank. If the system is an

Ultra-Cut XT using the Auto Gas Control, DFC 3000, the display

will show “0” until a process has been loaded. If there is a fault or other status showing the display will alternate

between the current setting and the fault.

The

Pilot PCB contains a pair of parallel IGBT transistors working as an electronic switch to connect and disconnect

the torch tip from the 1st inverter section.

When the pilot electronic switch is closed and the pilot is ignited by the Arc Starter, current from the 1st section

flows between electrode and tip. Then as transfer begins, a small current from the 2nd inverter flows from elec-

trode to work. When transfer is detected the pilot switch is opened and current from the 1st section is free to flow

to the work through the diode which is also on the Pilot board. The Pilot PCB also contains a pilot current sensor

to detect and measure the level of pilot current. Additional resistor/capacitor (RC) circuits on the pilot PCB assist

and stabilize the pilot and transferred arcs.

Advertising