SECTION TSM 630.4

ISSUE

D

PAGE 7 OF 10

1. Input power for the controller must be 240VAC,

single phase, 60 Hz or 220VAC, single phase, 50 Hz.

2. Controller terminals

a. 18 to 12 AWG wire size for heaters and controller.

Use appropriate thermocouple wire for thermocouple

and application.

b. Torque to 7.0 lb-in (0.8 Nm)
c. Wire strip length 0.30 in (7.6 mm).

3. Relay input terminals for use with N size pump only

(terminals 7-16)
a. 24 to 16 AWG wire size
b. Torque to 4.4 lb-in (0.5 Nm)
c. Wire strip length of 0.22 in (5.5 mm)

4. Relay line and load terminals for use with N size pump

only (terminals 1-6)
a. Will accept 18 to 8 AWG wire size
b. Torque to 12 lb-in (1.4 Nm)
c. Wire strip length 0.25 in (6.35 mm)
d. Retorque after 48 hours to minimize wire cold flow

e. Retorque terminals every 3 to 6 months
f. Ground terminal use spade terminal for No. 8 screw,

with upturned lugs

g. Attach grounding wire to grounding screw (#6)

5. Maintain electrical isolation between thermocouple analog

input 1 (terminals S1 and R1), any digital inputs-outputs,

and process outputs 1 and 2 (terminals L1, K1 and L2,

K2, respectively) to prevent ground loops.

6. To prevent injury and damage to the controller, do not

connect wires to unused terminals.

7. The wires for the heat cartridges can be joined together in

a junction box, and a single wire from the junction box can

be connected to the controller.

8. The wiring diagram is only valid for standard type J

thermocouples and controllers supplied from Viking Pump.

9. For information on the location and installation of the heat

cartridges and thermocouple, please see the TSM for

your specific pump. The thermocouple will require a fitting

adapter which is included with the controller kit in order to

mount to the pump.

NOTES:

FIGURE 4 - CONTROLLER TERMINAL LOCATIONS

FIGURE 5 - RELAY TERMINAL LOCATIONS

(FOR N SIZE PUMP ONLY)

TAbLE 1 - CONTROLLER TERMINAL DESCRIPTIONS

TAbLE 2 - RELAY TERMINAL DESCRIPTIONS

(FOR N SIZE PUMP ONLY)

Slot A

Slot C

L1

Normally Open

(Not Ready Light)

98

Power Input; AC; Fused

(Controller)

k1

Common

(Ready Light / Pump Interlock)

99

Common (Controller)

J1

Normally Closed

(Ready Light)

CF

Not Used

L2

Power Output; Fused

(Heat Cartridges)

CD

Not Used

k2

Common

(Heat Cartridges)

CE

Not Used

T1

Not Used

b5

Not Used

S1

Negative Thermocouple Lead

(Usually red wire used)

D6

Not Used

R1

Positive Thermocouple Lead

D5

Not Used

Relay Terminal Definitions

1

Not Used

2

Power Input; AC; Fused (From Power Source)

3

Common

4

Not Used

5

Heater

6

Heater

7

Power Input (From Controller)

8

Common

9 - 16

Not Used