Technical data, Troubleshooting, Controller – Viking Pump TSM630.4: K-QS 124E Controller User Manual

Page 9: Relay

Advertising
background image

SECTION TSM 630.4

ISSUE

D

PAGE 9 OF 10

TECHNICAL DATA -

Controller

TECHNICAL DATA -

Relay

TROUbLESHOOTING

Weight

6.6 oz. (186 g)

Supply Voltage

1x220-240 (±10%)

Frequency

50 or 60 Hz

Power Consumption

Max 10 VA

Fuses

Use Max 15 A

Terminal Wire Size

Use 18 to 12 AWG

Terminal Tightening Torque

7 lb-in (0.8 Nm)

Max Temperature Error @ Ambient ± 3.15°F (1.75 °C)
Sampling Rates for Input & Output 10 Hz
Heater Relay (L2,k2)

NO-ARC 15A, Form A

Ready Light Relay (L1,k1)

Mechanical Relay 5A, Form C

Operating Temperature

0-149°F (-18-65°C)

Storage Temperature

-40-185°F (-40-85°C)

Allowable Humidity

0 to 90%; non-condensing

Protection Class

NEMA 4X/IP66 if installed correctly (see

assembly step 4)

Pollution Degree

Pollution Degree 2

back-up battery Information

• Allows for data retention upon power failure

• Battery Type: lithium (recycle properly)

• Typical Battery Life: three cumulative years

of unpowered life at 77°F (25°C)

Agency Approvals

• UL® Listed to UL® 61010-1 File E185611

• UL® Reviewed to CSA C22.2 No.61010-1-04

• UL® 50 Type 4X

• FM Class 3545 File 3029084 temperature

limit switches

• CE, RoHS, and W.E.E.E. compliant

• Suitable for use in Class 1, Div 2, Groups A,

B, C and D or non-hazardous locations only.

Temperature Code T4A

• UL® Listed to ANSI/ISA 12.12.01-2007 File

E184390

• CSA approved; CSA C22. No. 24 File

158031 Class 4813-02

• UL® reviewed to Standard No. CSA C22.2

No. 213-M1987

Weight

1.6 lbs (0.7 kg)

Supply

Voltage

85V minimum -

660V maximum

Frequency

50 or 60 Hz

Power

Consumption 1.2 watts per amp switched
Storage

Temperature -40 - +185°F (-40 - +85°C)
Allowable

Humidity

0 to 90%; non-condensing

Protection

Class

IP20

Pollution

Degree

Pollution Degree 2

Classification Power Control; Installation III
Agency

Approvals

• UL® 508 Listed and C-UL®,

File E73741

Error Code

Description

Possible Causes

Corrective Action

Error Input

Sensor does not provide a valid signal

to controller

1. Thermocouple improperly wired or open 1. Correct wiring or replace thermocouple

No heat

action

Output does not activate load

1. Output is incorrectly wired

2. Load, power, or fuse is open

3. Set point is incorrect

4. Heat cartridge is burnt out*

1. Correct output wiring

2. Correct fault in system

3. Adjust set point to correct temperature

4. Replace heat cartridge

No display

No display indication or LED illumination 1. Power to controller is off

2. Fuse open

3. Breaker tripped

4. Safety interlock switch open

5. Wiring error

6. Incorrect voltage to controller

1. Turn on power

2. Replace fuse between power source and controller

3. Reset breaker

4. Close interlock switch

5. Correct wiring issue

6. Check voltage requirements and apply correct voltage

Temperature

runaway

Process value continues to increase

past set point

1. Thermocouple reverse wired

2. Controller output wired incorrectly

3. Short in heater

4. Power controller connection to controller

defective

5. Controller ouput defective

1. Correct thermocouple wiring (red wire negative)

2. Verify and correct wiring

3. Replace heater

4. Replace or repair power controller

5. Replace or repair controller

Device Error

Controller displays internal malfunction

message at power up.

1. Controller is defective

1. Replace or repair controller

* Use an ohmmeter or multimeter to determine the resistance across the

heat cartridge. A burnt out heater will have a reading of infinity (∞) ohms.

The customer supplied fuse between the heat cartridges and controller

will typically blow when one of the heat cartridges fails