9-2980 Without Electronics

(not shown)

2980

Adjust Spring Power According to Chart

This valve

controls

Door Speed

This valve

controls

Latching

Speed

This valve

controls

Backcheck

Use 1/8" hex

socket wrench

to adjust valves

1. Assemble (3) short cover screws

(#8-32 x 5/16") into bottom of

closer body and cover mounting

bracket. Approx. one turn

CAUTION: Avoid

interference with

electronics and wires

during installation of cover

2. Install cover onto back plate

and closer assembly and

secure with screws

Turn the spring adjusting nut clockwise the required number of turns to match

door width as indicated in chart. Where strong drafts exist, increase spring power

as needed. 351 Series door closers leave the factory with the spring adjustment

set at eight (8) turns

First, adjust closers as directed

in steps D and E

Adjustment Instructions

To regulate closer: Turn valve screw clockwise to slow down,

or counterclockwise to speed up door movement

CAUTION: Set valve for a slight cushioning effect. It is damaging to the closer if the

checking action is too abrupt. Backcheck should never be used in lieu of a door stop

E

D

To Install Cover

F

The intensity of backcheck action is

regulated by valve shown. Turn clockwise

to increase – or counterclockwise to

decrease checking

Clockwise Turns

of Adjusting Nut

8
8

12
16

Maximum adjustment is

approximately 20 turns.

Do not forcibly extend

adjustment beyond limits.

12-2980

Test

Button

On/Off

Switch

5/8" Nut

CAUTION

Typical Wiring

1. DISCONNECT ALL POWER BEFORE BEGINNING INSTALLATION

TO PREVENT ELECTRICAL SHOCK AND EQUIPMENT DAMAGE

2. INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE

PERSON

Stand Alone Units 2980

• Wire stand-alone unit to appropriate

power supply and fire alarm

• Refer to data sticker for proper

input voltage and current specifications

• Energize power supply

• Open door to hold-open point.

Door should hold open

• Depress On/Off Switch. Door should

close and latch

• Adjustment of spring power may be

necessary to ensure proper latching

• Depress on/off switch again.

Open door to hold open postion.

Door will hold open

3. ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL

ELECTRICAL CODES, ORDINANCES AND REGULATIONS

4. MAXIMUM WIRE SIZE IS 18AWG

For 9- companion units refer to

A7408 wiring Instructions

• Companion units are designed to work with

smoke detector units (12-2960, 12-2980, 12-2990,

12-2970) only.

• Wire companion unit to smoke detector unit

as shown on wiring diagram.

• Do not disconnect any existing wires on smoke

detector unit’s terminal strip.

• Energize power supply.

• Open doors to hold open point.

Doors should hold open.

• Depress On/Off button on smoke detector unit.

Doors should close and latch.

• Adjustment of spring power may be necessary

to ensure proper latching.

Opening for

Concealed Wiring

Earth Ground

Negative (-)

Positive (+)

3

2

1

Appropriate

Power Supply

Data

Sticker

Optional Remote

Release Connection

On/Off

Switch

Terminal Strip

for Power Input Connections

6

Companion Units

Smoke Detector Unit

Opening for

Concealed Wiring

Wire

Nut

7

9

UL

UL

Note: Caution input power supply must
match circuit board voltage rating,either
24VAC/VDC or 120 VAC

2

A7396D

Copyright © 2005, 2008, 2012, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved.

Reproduction in whole or in part without the express written permission of Sargent Manufacturing Company is prohibited.