Wiring Instructions for the

2900 Series FIREGUARD

®

Combination Door Closer-Holder and Releasing Device

with Integral Smoke Detector

CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE.

For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com

CAUTION

INSTALLER: LEAVE INSTRUCTION with building owner.

•

Wire 12- smoke detector unit to appropriate
power supply and fire alarm

•

Refer to data sticker for proper input voltage
and current specifications

•

9- Companion units are designed to work with
12- smoke detector units (12-2960, 12-2990,
12-2980) only

•

Wire companion unit to 12- smoke detector
unit as shown on wiring diagram if required

•

Do not disconnect any existing wires on
smoke detector unit’s terminal strip

•

Energize power supply. Current draw
.1 AMP per 12- unit.

•

Open door(s) to hold-open point.
Door(s) should hold open

•

Depress On/Off test switch on circuit
board. Doors should close and latch

•

Adjustment of spring power may be
necessary to ensure proper latching

•

Depress On/Off test switch to
reactivate hold open latch
assembly(s)

A7408B

1

1. DISCONNECT ALL POWER BEFORE BEGINNING

INSTALLATION TO PREVENT ELECTRICAL SHOCK AND
EQUIPMENT DAMAGE.

2. INSTALLER MUST BE A TRAINED, EXPERIENCED

SERVICE PERSON.

3. ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL

ELECTRICAL CODES, ORDINANCES AND REGULATIONS.

4. MAXIMUM WIRE SIZE IS 18AWG.

Wiring 12- Units with and without 9- Companion Unit

9- Companion Unit
(If required)

Field wiring by others

Wire nut

On/Off Test switch

Yellow

Red

Black

Yellow

Black

Black

Terminal strip for
power input wiring

Red

Yellow

Smoke
detector
unit

12- Smoke Detector Unit

9

1112

14

3 7

RED LED/
Reset Switch

Data
Sticker

Opening
for
surface
or
concealed
wiring

Line

Neutral

Earth Ground

120VAC

Power

Supply

*120VAC
Circuit Board
shown

Self
resetting
fuse

Wire the appropriate Power Supply
to circuit board. Power is either
120VAC or 24VDC/VAC depending
on circuit board supplied.

When 24VDC/VAC board is supplied,
wire 24VDC/VAC power supply to
+ and - terminals on circuit board.

*CAUTION: Refer to data
sticker on circuit board for
proper input voltage required.

Do NOT wire 120VAC power
to 24VDC/VAC circuit board.

Earth ground connection is required
when 120VDC power is used

*120VAC

wiring shown

Circuit board 120VAC
or 24VAC/DC
(120VAC shown)

Remove jumper and install
output connector assembly
(Part No. 63-2868) required
for this option

User supplied normally
closed momentary switch

Wiring Optional Remote Push Button