5 circuit polyswitches and fusing, 4 emergency release – SARGENT Battery Packs 737 User Manual

Page 2

Advertising
background image

800-810-WIRE (9473) • www.sargentlock.com • A7840B

02/26/09

Copyright © 2009, Sargent Manufacturing Company

, an ASSA ABLOY Group company

. All rights reser

ved.

Reproductions in whole or in part without express written permission of Sargent Manufacturing Company is prohibited.

2

SARGENT 3520 SERIES POWER SUPPLIES
OPERATION AND INSTALLATION INSTRUCTIONS

MODELS: 3520 (24 VOLT); 3521 (12 VOLT) SUPPLIES;

and 737-12 VOLT and 738-24 VOLT BATTERY BACKUP KITS

A DC short will not damage the power supply,

but the load will be shut off. To protect against a

short circuit when batteries are being employed,

a 2.5 Amp DC Polyswitch breaker is provided.

The Polyswitch functions as an automatic circuit

breaker. If it receives an overload, it rapidly cuts

the current down to a small leakage current

(about 100 mA). If this happens there is a reset

procedure. All loads must be removed from the

Polyswitch for a period of 10 seconds. This is

accomplished by simply disconnecting the load

wiring from the ”DC+” or “DC-” terminal. A short

circuit condition must be corrected in order for the

Polyswitch to reset.

3.5 CIRCUIT POLYSWITCHES AND FUSING

The power supplies have a 1 Amp AC Line Voltage Fuse and a 2.5 Amp DC Polyswitch. The AC fuse is on the hot 120 VAC

input and protects against a transformer internal short. A short in the DC load will not blow the AC fuse as the power supply

is short-circuit protected. The unit will shut off, if more than its rated output is attempted to be drawn.

3.4 EMERGENCY RELEASE

Factory setting is 12 volts for 12 volt unit and 24 volts for the 24 V unit. Emergency

release of DC output at the power supply is accomplished by using the unconnected “F”

terminal. Connect the contacts of the release switch between “DC+” and “F” and then

connect the load to “DC-” and “F”. When the emergency release contacts open, all DC

power will be cut off. When used with a UL listed fire alarm system, use auxiliary latching

normally closed contacts.
Note: Do not use “trouble” contacts (Fig. 2). * A trouble contact is a contact closure that

comes from the fire panel. A trouble contact is energized when a fire panel

experiences an integrity issue either internal to the panel or wiring to the panel.

Fig. 1 Load Wiring and

Emergency Switch Contact

Note: Connect DC+ load to F terminal when

adding switch for emergency release.

Load

N/C

Normally

Closed Switch

DC- DC+

TB2

3.6 ADDING BATTERIES TO A 3500 SERIES POWER SUPPLY

To connect batteries, follow these directions:

1. Install batteries as shown (Fig. 3).
2. The voltage adjustment potentiometer V.ADJ (Fig. 2) must be set without the

batteries connected. The voltage should be read at the flying leads of the

battery connection.

3. Set the voltage output by rotating the V. ADJ potentiometer on the power

supply module to 13.5 volts for 12 volt supplies; and 27 volts for 24 volt

supplies (Fig. 2).

4. IMPORTANT: Cutting and removing the WARNING label is necessary to make

connection and indicates understanding and acceptance of the conditions

and settings necessary for proper operation.

5. Connect the black flying lead to battery negative (-) and the red flying lead to

battery positive (+) (Fig. 2).

Fig. 3 Power Supply With Batteries Installed

+

-

+

-

115 VAC Input

Line Voltage

Fuse (1AMP)

Connector to

“Power On” LED

Voltage

Adjustment

Low Voltage AC

From Transformer

DC (-)

DC (+)

Unconnected Terminal

For Switch Connection

Optional

Battery Pack

2.5 AMP

Polyswitch Breaker

G
H

N

Fuse

Hot

Neutral

Gr

ound

+

-

Advertising