Environmental

NOTE: For additional information about environmental measurements for specific system configurations, see
dell.com/environmental_datasheets.

Standard Operating Temperature

Continuous operation: 10 °C to 35 °C at 10% to 80%
relative humidity (RH), with 26 °C max dew point. De-rate
maximum allowable dry bulb temperature at 1 °C per 300
m above 900 m (1 °F per 550 ft).

Expanded Operating Temperature

NOTE: When operating in the expanded temperature
range, system performance may be impacted.

NOTE: When operating in the expanded temperature
range, ambient temperature warnings may be
reported on the LCD and in the System Event Log.

< 10% of annual operating hours

5 °C to 40 °C at 5% to 85% RH with 26 °C dew point.

NOTE: Outside the standard operating temperature
(10 °C to 35 °C), the system can operate down to 5 °C
or up to 40 °C for a maximum of 10% of its annual
operating hours.

For temperatures between 35 °C and 40 °C, de-rate

maximum allowable dry bulb temperature by 1 °C per 175

m above 950 m (1 °F per 319 ft).

< 1% of annual operating hours

–5 °C to 45 °C at 5% to 90% RH with 26 °C dew point.

NOTE: Outside the standard operating temperature
(10 °C to 35 °C), the system can operate down to –5 °C
or up to 45 °C for a maximum of 1% of its annual
operating hours.

For temperatures between 40 °C and 45 °C, de-rate

maximum allowable dry bulb temperature by 1 °C per 125

m above 950 m (1 °F per 228 ft).

Expanded Operating Temperature Restrictions

Do not perform a cold startup below 5 °C.

The operating temperature specified is for a

maximum altitude of 3050 m (10,000 ft).

PCIe SSD is not supported.

GPU is not supported.

LRDIMM is not supported.

130 W (4 core) processor is not supported.

Redundant power supplies are required.