Riser diagram – Detex V50 EE User Manual

Page 19

Advertising
background image

104832 Page 19

RISER DIAGRAM

DETEX FILTERED AND REGULATED POWER SUPPLY

WITH FIRE ALARM SYSTEM LOOP 24 VDC @1 AMP MIN

DETEX REQUIRES THE POWER SUPPLY BE LOCATED

WITHIN 40 FEET OF THE DEVICE

REQUIREMENTS:

MIN. 22 GA STRANDED WIRE FOR SIGNALING

MIN. 18 GA STRANDED WIRE FOR POWER

DETEX DELAYED EGRESS

PANIC HARDWARE

INSTALLED BY

TRAINED TECHNICIAN

DOOR SIGN SUPPLIED WITH

DETEX DELAYED EGRESS

PANIC HARDWARE

REFER TO WIRING &

FIRE ALARM DIAGRAMS

FOR WIRING

INSTRUCTIONS

J

PROVIDE WIRING CONDUIT, CONNECTOR,

ETC BETWEEN DETEX POWER SUPPLY

AND FIRE ALARM CONTROL PANEL AS

REQUIRED TO ALLOW THE FIRE ALARM

SYSTEM TO OVERRIDE THE DETEX

DELAYED EGRESS FEATURE DURING

A FIRE ALARM.

THE LOSS OF POWER OR OPEN FIRE

ALARM CIRCUIT WILL ELIMINATE THE

DELAYED EGRESS FUNCTION