Delayed egress operations, Arming and authorized exit disarming, Low battery indication – Detex V50 EE User Manual

Page 21

Advertising
background image

104832 Page 21

NORMAL OPERATION

NUISANCE DELAY

EXITING UNDER ALARM

BATTERY BACKUP FOR ALARM

Turn Key CW To Disarm

Red LED while alarming

ARMING AND AUTHORIZED EXIT

DISARMING

Glowing Green LED

Turn Key CCW To Arm

DELAYED EGRESS OPERATIONS

With door closed, insert key in the cylinder, turn CCW, then back to the home key position and remove it. LED glows

green. Authorized personnel can exit the door during the arming delay. After a 1, 5 or 15

second arming period, alarm issues three quick beeps and LED goes off, indicating that the unit is armed.

Insert key, turn CW to a stop. Green LED will blink twice to indicate the unit is disarmed.

To exit, push and maintain pressure on the pushpad. After a one-second delay, (nuisance delay), LED flashes RED

and alarm pulses on and off for 15 seconds. After 15 seconds, alarm issues short and long pulses to indicate that

one can exit by depressing the pushpad.

Alarm sounds continuously and LED is steady RED. Turn key CW to stop alarm. In case of fire, the fire alarm

over-rides the 15 second delay and the door opens without delay when the pushpad is pushed.

A 9-volt battery is included as a backup power source for the alarm siren if power is lost.

To disable low battery indication, slide the DisLoBat switch to 'ON'. See page 16 for location.

LOW BATTERY INDICATION

If battery voltage is low(7 volts or less), unit remains armed but LED flashes RED and unit beeps twice every

45 seconds. Replace battery as soon as possible.

Indicates the unit is in process of arming. The siren will chirp three times to indicate the unit

is armed and green LED will turn off

DOUBLE BLINK

DOUBLE CHIRP

OFF

LED COLOR

SLOW BLINKING

FAST BLINKING

ON

ON

OFF

RED
OFF

Pushpad is depressed, delay to open started

This indicates either armed or disarmed

Delay to open expired, door has been opened

ON

SLOW PULSE

FAST PULSE

OFF

OFF

OFF

ON

OFF

SIREN SOUNDS

THREE CHIRPS

GREEN

ON

FUNCTION

BLINK

BLINK

OFF

OFF

Low Battery - every 45 seconds

Delay to open expired

Factory installed jumper removed from 3 & 4 terminals

Armed - status ON

Disarmed - status ON

PushPad

Home
Key
Position

Red LED

Siren

Green LED

Mortise

Cylinder

(LHR shown)

When pushpad is depressed for less than 1 second, alarm will emit a single pulse but will not start delay function.

Advertising