TROUBLESHOOTING

For further assistance, contact Detex Technical Support 1-800-729-3839

Probable Cause

Turn key clockwise to OFF position.

Confirm strike is pushing in dead latch. Door must be closed.

Confirm 24VDC power on the delayed egress device main board

terminals 1(+) & 2(-).

Confirm closed fire loop connection on power supply.

Confirm cable is plugged in properly.

Confirm the mortise cylinder is functioning correctly.

Confirm closed fire loop connection on power supply.

Confirm the 2-pin header with the two red wires are plugged into the

delayed egress main board.

Confirm 24VDC power on the delayed egress device main board

terminals 1&2.

Factory installed jumper removed from terminals 3 and 4.

Check battery. If no battery is needed, slide DisLoBat switch on

delayed egress main board to 'ON'. See electrical pages of instructions.

Problem

Alarm sounds when power is applied:

No green light when key is turned CCW:

No delayed egress:

Both red and green lights on:

Low battery signal-

Two chirps every 45 seconds: