Wine Guardian Ducted Split Wine Cellar Cooling Systems (WGS175) - Manual User Manual

Page 55

Advertising
background image

57

Room sensor
calibration

Setting 15

Press “Settings” button to advance to Setting 15.

Press the “Up” or “Down” buttons to adjust to the
desired set point. Maximum setting is +2°C,
minimum setting is -2°C. Factory default is zero
(0). Sensor calibration set point changes the actual
display reading (temperature only) by the value of
this setting.

Example: Sensor reading = 13 Deg C

Setting 15 set to +2
Display reading = 15 Deg C

Differential
temperature
adjustment

Setting 16

Press “Settings” button to advance to Setting 16.

Press the “Up” or “Down” buttons to adjust to the
desired set point.

This setting changes the system/compressor turn-on
temperature above set point. Factory default is set to
1°C.
Example: Sensor reading = 13°C

Setting 16 set to +1°C
System/compressor turns on at 14 Deg. C.

Deadband setting

Setting 17

Press “Settings” button to advance to Setting 17.

Press the “Up” or “Down” buttons to adjust to the
desired set point.

This setting is the minimal allowable temperature
difference between heating and cooling set points.
Maximum is 3°C, minimum is 1°C. Factory default is
set to 1°C

Test mode setting

Setting 18

Press “Settings” button to advance to Setting 7.

Press the “Up” or “Down” buttons to adjust to the

desired set point. When set to one (1) the
controller will automatically turn on all outputs

with the exception of electric heat. Factory default
is zero (0).

Zero (0) = Off (0)

One (1) = On 一(1)

System Selection 系统
的选择

DO NOT CHANGE






Advertising