Instructions to reset high pressure switch – Wine Guardian Ducted Split Wine Cellar Cooling Systems (WGS175) - Manual User Manual
Page 71
Advertising

73
Instructions to Reset High Pressure Switch
Remove the access panel, grille or duct collar at the condenser opening labeled “High
Press. Manual Reset Switch ----- “Remove panel or grille to access”
Locate the high pressure switch near the compressor (a cylindrical device piped into
the refrigeration system with two wires a red button on the top).
Push in the button until it locks into position.
Push the rocker switch to restart the unit.