Advanced Troubleshooting

IMPORTANT

THIS SECTION IS INTENDED FOR QUALIFIED REFRIGERATION SERVICE TECHNICIANS ONLY.

THE TECHNICIAN SHOULD REPEAT ALL OF THE PREVIOUS TROUBLESHOOTING STEPS

BEFORE TAKING ACTION ON THESE MORE TECHNICAL SOLUTIONS.

Evaporator Coil is Freezing


Possible Cause

Solution

Charge too low Check sight glass
Check for leaks
Add refrigerant

High Pressure Switch Keeps Tripping Even After Checking for
obstructions and Dirty Filters/Coils

Possible Cause

Solution

Condenser fan not operating Repair or replace

Unit Cycles on and off more than 8 times/hr

Possible Cause Solution

Thermostat malfunctioning Check the thermostat guide for thermostat
information

Low suction pressure Check low pressure switch
Check pressure and adjust superheat