Other Miscellaneous Problems

Unit operates but the power switch light is not ON

Possible Cause Solution

Bulb is burned out Replace bulb

Unit is leaking water

Possible Cause Solution

Trap plugged Clean trap

Condensate pan plugged Remove blockage and clean

Unit not level Level with shims

Unit is running properly, but the sound of the unit is objectionable

Possible Cause Solution

Noise is from airflow Redirect airflow
Add baffles

Add insulated ductwork

Noise is from unit

Add sound baffle between unit and occupied

space

High Pressure Switch has Shut the Unit Down

Every Wine Guardian unit has a manual reset high pressure switch in the refrigeration system.
This switch shuts the compressor and condenser down if the head pressure in the system is too
high. It is intended to protect the compressor. Restricted airflow through the condenser is the
most common reason for the pressure to become too high. This can be caused by dust covering
the filter or an obstruction blocking the airflow in the duct or grille.

Possible Cause

Solution

Head Pressure in unit is too high because

Remove the obstruction in the duct or grille or

an obstruction is restricting air flow

clean the filter. Then restart the unit after
resetting the using the high pressure switch.