3. Commissioning

Î Establish the power supply
During a short initialization phase, the operating control lamp
flashes red and green.
When the controller is commissioned for the first time or after
a reset, it will run a commissioning menu. The commissioning
menu leads the user through the most important adjustment
channels needed for operating the system.
Operating the commissioning menu:

Î Enter the channel by pressing button 3
The

symbol flashes.

Î Adjust the value by pressing buttons 1 and 2

Î Save the adjustment by pressing button 3 again
The

symbol stops flashing.

Î Press button 1 or 2 to switch to the next or previous channel

1

2

3

(SET)

The three push buttons of the BS/2 controller

The commissioning menu consists of the following 4 channels:

1. Language

Î Adjust the desired menu language in this channel
dE : German
En : English

LANG:
Language selection
Selection: dE, En
Factory setting: En

2. Unit

Î Adjust the unit in which temperatures and temperature

differences shall be displayed

UNIT:
Temperature unit selection
Selection: °F, °C
Factory setting: °C

3. Maximum tank temperature

Î Adjust the desired maximum tank temperature

S MX:

Maximum tank temp.
Adjustment range:
40 ... 200 °F

[4 ... 95 °C]

in steps of 2 °Ra [1 K]
Factory setting:140 °F [60 °C]

Note:
The controller is also equipped with a non-
adjustable emergency shutdown function, which
will shut the system down if the tank reaches
200 °F [95 °C].

4. Minimum pump speed

Î Adjust a minimum speed for the pump

nMN:
Pump speed control
Adjustment range: 30 ... 100
in steps of 5 %
Factory setting: 30

Note:
If a load which is not speed-controlled is used, the
value must be set to 100 %.