STIEBEL ELTRON SOM 6 PLUS User Manual

Page 6

Advertising
background image

6

S1

S2

S4 / TR

The controller calculates the temperature difference between
collector sensor S1 and tank sensor S2. If the difference is
larger than or identical to the adjusted switch - on temperature
difference (DT O), the solar pump will be operated by R1,
and the tank will be loaded until the switch-off temperature
difference (DT F) or the maximum tank temperature (S MX)
is reached.

R1

S3

1.4 Terminal allocation

Display Channels
Channel

Description

Terminal

Page

INIT

x*

ODB initialization active

-

12

FLL

x*

ODB filling time active

-

12

STAB

x*

ODB stabilization in progress

-

12

COL

x

Temperature collector

S1

12

TST

x

Temperature tank

S2

12

S3

x

Temperature sensor 3

S3

12

S4

x

Temperature sensor 4

S4

12

TR

x*

Temperature return sensor

S4

12

n %

x

Pump speed R1

R1

13

hP

x

Operating hours R1

R1

13

kWh

x*

Heat quantity kWh

-

13

MWh

x*

Heat quantity MWh

-

13

Sensors S3 and S4 can optionally be connected for
measurement purposes.
If energy metering (OHQM) is activated, sensor S4 has to be
connected as return sensor.

S1

S3

S2

S4/TR

R1

exemplary

Drainback system layout