Energy metering

OHQM: Energy metering
Adjustment range: OFF / ON
Factory setting: OFF

If OHQM is activated, the heat quantity gained can be
calculated and displayed. Energy metering is possible if a
flowmeter is used. To enable energy metering, proceed as
follows:

Î Read the flow rate (l/min) from the flowmeter at maximum

pump speed and adjust it in the

FMAX channel

Î Adjust the heat transfer fluid and the concentration of the

antifreeze in the channels

MEDT and MED%.

FMAX: Flow rate in l/min
Adjustment range: 0.5 ... 100.0
in steps of 0.5
Factory setting: 6.0

MEDT: Heat transfer fluid
Adjustment range: 0 ... 3
Factory setting: 1

MED%: Antifreeze ratio
in Vol-% (MED% is hidden
when MEDT 0 or 3 is used.)
Adjustment range: 20 ... 70
in steps of 1 %
Factory setting: 45

Heat transfer fluid:
0 : Water
1 : Propylene glycol
2 : Ethylene glycol
3 : Tyfocor

®

H-30 L/LS