STIEBEL ELTRON SOM 6 PLUS User Manual

Page 18

Advertising
background image

18

Time period - switch-on conditions
tDTO
:
Time period -
switch-on conditions
Adjustment range: 1 ... 100 s
in steps of 1 s
Factory setting: 60 s

The parameter

tDTO is used for adjusting the time period

during which the switch-on condition

DT O must be

permanentely fulfilled.

Filling time
tFLL
:
Filling time
Adjustment range:
1.0 ... 30.0 min
in steps of 0.5 min
Factory setting: 5.0 min

The filling time can be adjusted using the parameter

tFLL.

During this period, the pump runs at 100 % speed.

Stabilization
tSTB
:
Stabilization
Adjustment range:
1.0 ... 15.0 min
in steps of 0.5 min
Factory setting: 2.0 min

The parameter

tSTB is used for adjusting the time period

during which the switch-off condition

DT F will be ignored

after the filling time has ended.

Drainback option

A drainback system permits the heat transfer fluid to drain
back into the holding tank when solar energy is not collected.
The drainback option will initiate the filling of the system
when solar loading begins.
If the drainback option

ODB is activated, the pump will

operate at 100 % speed for the adjusted filling time

tFLL in

order to fill the system with fluid from the holding tank. After
tFLL, pump speed will go down to the adjusted minimum
pump speed

nMn. The switch-off conditions will then be

ignored for the stabilization time

tSTB in order to avoid the

system from shutting down prematurely.
If the function is activated, the menu items described in the
following (

tDTO, tFLL and tSTB) have to be adjusted:

ODB:
Drainback option
Adjustment range: OFF / ON
Factory setting: OFF

Note:
A drainback system layout requires additional
components such as a holding tank. The drainback
option should only be activated if all components
required are properly installed.

Note:
When the drainback option

ODB is activated, the

cooling functions

OCC, OSYC and OSTC as well as

the antifreeze function

OCF are not available.

If

OCC, OSYC, OSTC or OCF have already been

activated before, they will be deactivated again
as soon as

ODB is activated. They will remain

deactivated, even if

ODB is deactivated later on.

Note:
When the drainback option

ODB is activated, the

temperature differences

DT O, DT F and DT S are set

to a fixed adjustment. Additionally, the adjustment
range and the factory setting of the collector
emergency shutdown temperature

EM changes

(see the corresponding channel descriptions for
further information).
Previous adjustments made in these channels will
be overridden and have to be entered again if

ODB

is deactivated later on.