Troubleshooting – STIEBEL ELTRON SOM 6 PLUS User Manual

Page 20

Advertising
background image

20

5. Troubleshooting

Operating control lamp

Warning symbols

Operating control lamp flashes red. On the display the
symbols

and

appear.

VBus

®

terminals

power supply
terminals

fuse

load terminals

sensor terminals

ground
terminals

In the case of an error, a message is shown on the display of
the controller:

Sensor defect. An error code instead of
a temperature is displayed in the sensor
display channel.

- 88.8

888.8

Cable broken.
Check cable.

Short circuit. Check
cable.

Disconnected Pt1000 temperature sensors
can be checked with an ohmmeter. In the
following table, the resistance values with
the corresponding temperatures are shown.

Operating control lamp off.

Check the power supply. Is it disconnected?

no

The fuse of the controller
could be blown. It can be
replaced after the front
cover has been removed
(spare fuse is enclosed in
the accessory bag).

yes

Check the supply line and
reconnect it.

°C

°F

Ω

°C

°F

Ω

-10

14

961

55

131

1213

-5

23

980

60

140

1232

0

32

1000

65

149

1252

5

41

1019

70

158

1271

10

50

1039

75

167

1290

15

59

1058

80

176

1309

20

68

1078

85

185

1328

25

77

1097

90

194

1347

30

86

1117

95

203

1366

35

95

1136

100

212

1385

40

104

1155

105

221

1404

45

113

1175

110

230

1423

50

122

1194

115

239

1442

Resistance values of the Pt1000-sensors