5.1 Various

Pump starts for a short moment, switches off, switches on
again, etc.

Temperature difference at
the controller too small?

no

yes

Wrong position of collector
sensors?

yes

Change

∆Ton and ∆Toff

correspondingly. Problem
solved?

Mount the collector sensor
at solar flow (warmest
collector output); use
s e n s o r w e l l o f t h e
respective collector.

Pump starts up very late

The temperature difference between tank and collector
increases enormously during operation; the collector circuit
cannot dissipate the heat.

Collector circuit pump
defective?

no

yes

Heat exchanger calcified?

yes

Check / replace it

Decalcify it

no

Heat exchanger blocked?

yes

no

Clean it

Heat exchanger too small?

yes

Replace with correctly
sized one.

no

Plausibility control of
the option tube collector
special function

Change

∆Ton and ∆Toff

correspondingly.

Switch-on temperature
difference Ton to large?

no

yes

Non-ideal position of the
collector sensor (e.g. flatscrew
sensor instead of sensor in
sensor wells)?

no

Pump is overheated, but no heat transfer from the collector
to the tank, flow and return have the same temperature;
perhaps also air / gas bubbles in the lines.

Air in the system; in crease
the system pressure to at
least static primary pres-
sure plus 7. 25 psi (0.5 bar);
if necessary continue to
increase pressure; switch
the pump off and on for a
short time.

Air in the system?

no

yes

Is the collector circuit
blocked at the dirt trap?

yes

Clean the dirt trap

Activate tube collector
function if necessary.

yes

o.k.

yes

o.k.

Advertising