Attach ethernet to this connector, Compatible cables, Connecting the cable – KEYENCE DL-EP1 User Manual

Page 3: Specifications, Dimensions

Advertising
background image

3

z

Connecting to a large display type sensor amplifier

1

Connect the sensor amplifier to the EtherNet/IP Compatible Network Unit DL-EP1
using the optional expansion cable (OP-35361).

2

Detach the sensor amplifier connector (for DIN rail mounting type) of the
EtherNet/IP Compatible Network Unit DL-EP1 with pliers and mount the attached
expansion connector sticker.

Methods for connecting the DL-EP1 to the Ethernet are explained in this section.

„

Compatible cables

An STP (shielded twisted-pair) cable or UTP (unshielded twisted-pair) cable is used to con-
nect the DL-EP1 to the Ethernet.
The compatible cables differ when Ethernet is structured of 10BASE-T or 100BASE-TX.

„

Connecting the cable

Connect the network cable to the RJ-45 connector.

*1 "D-bus" is the name of KEYENCE's wiring-saving system for sensor amplifiers.
*2 Varies with the sensor amplifiers connected.

• Turn OFF the power before connecting the expansion cable

and connect securely. Diagonal or otherwise improper inser-

tion may damage the equipment.

• Inserting or pulling the cable when the power is turned ON

may damage the equipment.

Attach Ethernet to This Connector

Ethernet

Compatible cables

10BASE-T

STP cable or Category 3 or higher UTP cable

100BASE-TX

STP cable or Category 5 or higher UTP cable

• Use a straight cable when connecting DL-EP1 to the Ethernet switch.
• Use a cross cable when connect the DL-EP1 directly to a personal

computer.

Detach the
protection sticker

Detach the
protection
sticker

Expansion cable (cable length:300mm)

NOTICE

Sensor amplifier connector
(for DIN rail mounting type)

Expansion
connector
sticker

Reference

Specifications

Product name

EtherNet/IP Compatible Network Unit

Model

DL-EP1

Ethernet
Specifications

Compliant
standards

IEEE802.3 (10BASE-T)
IEEE802.3u (100BASE-TX)

Transmission rate

10Mbps (10BASE-T)
100Mbps (100BASE-TX)

Transmission
medium

STP cable or Category 3 or higher UTP cable
(10BASE-T)
STP cable or Category 5 or higher UTP cable
(100BASE-TX)

Maximum cable
length

100 m (Distance between DL-EP1 and Ethernet switch)

Maximum number
of connectable
hubs

4 (10 BASE-T)
2 (100 BASE-TX)

EtherNet/IP
Specifications

Compatible
functions

Cyclic communication

Compatible with UCMM and Class 3 messaging
(Explicit messaging)

Number of
connections

64

RPI
(Transmission
cycle )

0.5 to 10000 ms (0.5 ms unit)

Tolerable
communication
bandwidth for
cyclic
communication

6000 pps

Conformance test Compatible with Version A7

Sensor
connection
specifications

Connectable
sensors

Sensor amplifiers with D-bus support

*1

Number of
connectable
sensor units

15 units max

*2

Indicator lamps

Link/activity indicator (LINK/ACT)?Green LED
Module status indicator (MS)?2-color (green/red) LED
Network status indicator (NS)?2-color (green/red) LED
Sensor communication indicator (N-bus): 2-color
(green/red) LED

Power voltage

20 to 30 VDC ±10%, including ripple (p-p)10%
(supplied from the connected sensor amplifiers)

Power consumption

1500 mW or less (at 30 V 50 mA max)

Environmental
resistance

Operating
surrounding air
temperature

-20 to 55 °C (no freezing)

Operating
surrounding air
humidity

35 to 85% RH (no condensation)

Vibration
resistance

10 to 55 Hz compound amplitude 1.5 mm, 2 hours each
in X, Y, Z directions

Pollution degree

2

Materials

Main unit case: Polycarbonate

Weight

Approx. 70 g

Dimensions

25.6

35.4

43.5

94.5

38.1

(42.5

)

29.4

(mm)