8. Detection Mode Operation

General-purpose mode (F-1)

This mode allows the user to configure 2 detection points.
Control output 1: Turns ON when pressure exceeds setting P1.
Control output 2: Turns ON when pressure exceeds setting P2.

<Output 1>

P1

0

Output 1

OFF

ON

OFF

P2

0

OFF

ON

OFF

<Output 2>

Output 2

*Hysteresis when operating in general-purpose mode and application

modes 1 and 2 is 0.5% of F.S. in the standard and high-speed modes.
During focus mode operation, it is 0.1% of F.S.

Variable hysteresis mode (F-2)

Two detection points may be user-configured, and hysteresis for both
may also be set.
Control output 1: Turns ON when pressure exceeds setting P1. Turns OFF

when pressure drops the selected hysteresis amount
below P1.

Control output 2: Turns ON when pressure exceeds setting P2. Turns OFF

when pressure drops the selected hysteresis amount
below P2.

<Output 1>

P1

H1

Output 1

OFF

ON

OFF

0

P2

OFF

ON

OFF

H2

0

<Output 2>

Output 2

Window mode (F-3)

The user may select a pair of upper (Hi) and lower (Lo) thresholds, and
the sensor turns OFF when the pressure falls outside of the resulting
range.
*Control output 1 is 0.5% of F.S. during standard and high-speed

operation, it has a hysteresis of 0.1% of F.S. in the focus mode, and
control output 2 has a hysteresis of 0.

Hi

Lo

Output1/Output2

OFF

ON

ON

OFF

OFF

<Output 1/Output 2>

0

Application mode 1 (A-1)

This detection mode is optimum for use in suction detection applica-
tions.
Recommended heads: AP-41/41M/44
Control output 1: Suction pressure detection.

Turns ON when pressure exceeds setting P1.

Control output 2: Detection of vacuum burst pressure (or confirmation of

vacuum arrival pressure).
Turns ON when the pressure falls below setting P2. May
be set during focus mode operation, although there are
restrictions on the setting range.

Zero shift:

Shifts the zero point immediately after setting the zero
shift timer once zero shift input is received.

P1: Pressure setting for control output 1.
T1: Zero shift timer setting (ms) < Variable between 0 and 1,999 ms
P2: Pressure setting for control output 2.
*P2 is unrelated to zero shift and is always based on the current ambi-

ent pressure.

<Output 1>

P1

Output 1

OFF

ON

OFF

0

<Output 2>

0

Output 2

OFF

ON

OFF

P2

0

0

Shift

Zero shift input

T1

<Zero shift>

Application mode 2 (A-2)

This mode is optimum for use in leak test applications.
Recommended head: AP-43
Control output 1: Leak pressure detection.

Turns ON when pressure falls below setting P1.
*Output only when receiving zero shift input.

Control output 2: Window comparator output for detection of fill pressure.

Turns OFF when pressure falls outside the range deter-
mined by upper (Hi) and lower (Lo) thresholds. Fill pres-
sure values are displayed with the center pressure as 0
during focus mode operation.

P1: Pressure setting for control output 1.
Hi: Upper threshold setting for control output 2.
Lo: Lower threshold setting for control output 2.
*The Hi and Lo values are unrelated to zero shift and are always based

on the current ambient pressure.

<Output 1>

P1

Output1

Zero shift input

OFF

ON

OFF

ON

0

<Output 2>

Hi

Lo

Output 2

OFF

ON

OFF

OFF

ON

Analog
output (1 to 5 V)

0 V

Main

circuit

Blue

Pink

12 to 24 VDC

Main circuit

Pink

Brown

(Short-circuit current 5 mA or less)

AP-AO1 Panel mounting bracket

SET

AP-C33

MODE

MP

a

SET

AP-C40

MODE

MP

a

Panel mounting ring

Front protective
cover

Panel-mounted body

Panel-mounted body

Panel-mounted body

6. Connection Method and Diagrams

Insert the included connector-tipped cable into the sensor's connector.
Position the connector so that the side of the connector where the metallic
contacts are visible is facing up.

Side where the metallic

contacts are visible faces up.

Connector cable

Input/output circuit (AP-C40)

Input/output circuit (AP-C40P)

12 to 24 VDC

5 to 40 VDC

5 to 40 VDC

0V

Main circuit

Ov
ercurrent

protection circuit

Load

Load

Input/output

circuit

Analog output/
zero shift input: switchable

Brown

Blue

Black

White

Pink

12 to 24 VDC

0V

Load

Load

Main circuit

Ov
ercurrent

protection circuit

Black

White

Pink

Analog output/
zero shift input: switchable

Brown

Blue

Input/output

circuit

Analog output circuit

Zero shift input circuit

Zero shift input circuit

(AP-C40)

(AP-C40P)

(Short-circuit current 5 mA or less)

Main

circuit

Blue

Pink

7. Precautions for Safe Use

Follow these guidelines. Failure to do so may result in product damage.

CAUTION

Connections

Always ground the frame ground terminal when using an off-the-shelf
switching regulator.

Use separate conduits for power line and high voltage lines, since use
of a common conduit may result in device malfunction caused by noise.

Improper wiring may result in the device becoming excessively hot or
in device damage.

Notice about CE marking

Attach the ferrite core (OP-87505) if you extend a sensor head cable/
amplifier power cable to 3 m or more to use.
(Attachment position: within 100 mm from the amplifier unit of a
power cable, Number of turns: 2)

Other

Do not use this sensor with corrosive gasses or liquids.

Do not insert objects such as wire into the pressure insertion area.
Doing so may result in the device failing to operate properly due to
damage to the pressure-sensitive elements.

Do not use sharp-tipped objects to press the setting keys.