5.7 Diagnostics – Blocking (Err) Errors

Blocking errors are generated by a permanent fault. There is no way to unlock the unit other
than to resolve the cause of the fault.

To reset a lockout error, do the following:

Resetting the Unit after a Lockout Error

1. When the boiler goes into lockout, the

icon will show in the control panel display and

the burner icon(s) (

,

,

, or

) associated with the lockout will blink.

2. Press the

RESET

button once and the lockout error number will show in the display.

3. To resolve the error, consult the table of Error (Err) messages in Figure 5-8 and attempt to

diagnose and resolve the problem.

4. To return the display to normal function, press and hold down the

RESET

button for at least

5 seconds.