AM Series Boilers and Water Heaters

CHAPTER 3 – INSTALLATION

OMM-0100_0B

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 65 of 156

GF-146

Ph.: 800-526-0288

PRI - 07/14/14

3.16.5.3 Air Intake and Vent Starter Pieces

Venting must be supported per guidelines listed in the National Mechanical Code, Section 305,
Table 305.4 or as local codes dictate.

To connect a vent pipe to the air intake and vent outlet, proceed as follows while referring to
Figures 3-28 and 3-29:

Installing the Air Intake and Vent Connections

1. Install heater adapter “P” above inlet air opening “M” with gasket “D” and bolts “E”.

2. Make the connection between adapter “B” & “P” and pipe “G” & “N” as shown in Figure 3-28.

3. Insert the air inlet pipe 3” deep into the adapter “P” & “B”.

4. Tighten the clamp “F” to mechanically secure the adapter to the pipe.

Figure 3-28: Air Intake and Vent Connection Installation

Figure 3-29: Air Intake and Vent Connection Correctly Installed