AM Series Boilers and Water Heaters
CHAPTER 3 – INSTALLATION
OMM-0100_0B
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 51 of 156
GF-146
Ph.: 800-526-0288
PRI - 07/14/14
Figure 3-19: Condensate Box Draining
The condensate drainage system is designed to empty all the condensate produced by one
boiler only. Each boiler must be equipped with its own condensate drainage system or the
drainage system may malfunction
A condensate removal pump is required if the boiler is below the drain. When installing a
condensate pump, select one approved for use with condensing boilers and furnaces. The
pump should have an overflow switch to prevent property damage from condensate spillage.
3.13.1 Commonwealth of Massachusetts Special Requirement
When the boiler is installed and used in the Commonwealth of Massachusetts, a neutralization
unit MUST be installed in the condensate removal system.