Condensate System Inspection and Maintenance (Cont.)
8. Replace the condensate cover and reinsert the condensate collection box assembly back
into the unit.
WARNING!
The condensate collection box must be filled with water to prevent
flue gas emissions from escaping during unit operation. Failure to
comply with this requirement can result in dangerous levels of
carbon monoxide.
9. Open the manual gas shutoff valve.
10. Restore electrical power to the unit and return to service.
WARNING!
The condensate neutralizer box MUST be installed correctly into
the unit, as shown in Figures 2-3, 2-4, 2-5, and 2-6. If you do not
install the condensate collection box into its correct position, it will
result in combustion gases will entering the room and creating a
dangerous condition.