AM Series Boilers and Water Heaters
CHAPTER 3 – INSTALLATION
OMM-0100_0B
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 33 of 156
GF-146
Ph.: 800-526-0288
PRI - 07/14/14
Unpacking Instructions (Cont.)
4. Install the two factory supplied eyebolts “D” on the upper side of the unit and attach
chains or straps to lifting ring/hook “E” as shown in Figure 3-5.
Figure 3-5: Removing the Unit from Wood Pallet (Lifting)
Using the appropriate lifting equipment, hoist the unit from the wood pallet. The weight of each
models are as follows:
Model
Weight (lbs.)
AM399
291
AM500
302
AM750
511
AM1000
599
5. While unit is suspended, install the leveling feet “F” (Figure 3-6), to allow leveling the unit
after installation.
Figure 3-6: Installing the Leveling Feet
WARNING!
The floor onto which the unit is installed must
be capable of supporting the weight of the unit
or the unit and/or building may be damaged.