INSTALLATION

2-4

The pr ocedures to install and c onnect b oth of

the c ondensate drains ar e pr ovided i n

paragraphs 2.6.1 and 2.6.2.

SHELL DRAIN

VALVE

EXHAUST

MANIFOLD

REAR VIEW

A

A

B

B

CONDENSATE

TRAP

DRAIN

CONNECTING

MANIFOLD

DRAIN

UNIT

FRAME

CONNECTING

MANIFOLD

DRAIN

VALVE

CONDENSATE

DRAIN PIPE

TO

CONDENSATE

TRAP

SHELL

VIEW “B - B”

VIEW “A - A”

UNIT

FRAME

EXHAUST

MANIFOLD

CONDENSATE

TRAP

DRAIN

HOSE

CLAMP

1" I.D.

HOSE

TO FLOOR

DRAIN

Figure 2-5

Condensate Drain Connection Location

2.6.1 Exhaust Manifold Condensate
Drain

Refer to F igure 2- 5, V iew A – A a nd install as

follows:

1. Connect a length of 1 inch I.D. hose (part no.

91030) to the drain on the exhaust manifold

and secure it in place with a hose clamp.

2. Route the hose to a nearby floor drain.

2.6.2 Connecting Manifold Condensate
Drain

The c onnecting m anifold drain pi pe s hown i n

Figure 2-5, View B – B m ust be c onnected to a

separate c ondensate drain tr ap ex ternal t o th e

unit. T his c ondensate tr ap ( part n o. 24060) is

supplied with the un it along with a trap adapter

and a 3/4” NPT x 5” long nipple. Refer to Figure

2-6 and install the trap as follows:

NOTE

The c ondensate tr ap d escribed in the

following s teps c an be installed o n t he

floor behind the unit as shown in Figure 2-

6. Ensure that the condensate trap inlet is

level with or be low t he c onnecting

manifold drain pipe. Ensure that the outlet

hose f rom the tr ap s lopes awa y ( down)

from the trap.

1. Apply Teflon tape to the threads of the 3/4” x

5” long nipple provided with the boiler.

2. Attach t he 3/4” N PT nip ple b etween th e

condensate trap inl et and the tr ap ada ptor

(Figure 2-6).

3. Attach another 3/4” NPT nipple (not sup-

plied) to the condensate trap outlet on the

lower part of the trap.

4. Connect the condensate trap and adaptor to

the connecting manifold drain pipe. Position

the trap so it is level and then tighten the

thumb screw on the adaptor.

5. Place a suitable support under the

condensate trap to maintain the trap in the

level position.

6. Connect a length of 1” I.D. polypropylene hose

to the outlet side of the condensate trap and

route it to a nearby floor drain.


If desired, a Tee fitting may be used to connect the

two drain hoses from the exhaust manifold and the

outlet side of the of the condensate trap attached to

the connecting manifold.

If a floor drain is n ot available, a condensate pump

can be u sed to r emove the condensate to drain.

The m aximum co ndensate flow r ate i s 20 GPH.

The condensate dr ain t rap, associated fittings and

drain lines m ust be removable fo r routine

maintenance.