MAINTENANCE

STAGED

IGNITION

ASSEMBLY

3/8-16

NUTS (8)

BURNER

HOUSING

1/4-20

SCREWS

(6)

GROUNDING

SCREW

Figure 7-3

Burner Disassembly Diagram - Top View

NOTE

The bur ner hous ing is h eavy, weighing

approximately 25 pounds.

11. Refer to the ex ploded v iew in F igure 7- 4.

Remove the bur ner hou sing f rom bur ner

flange by pulling straight up.

12. Remove the grounding screw.
13. Remove the burner by pulling straight up.
14. Remove and replace the burner gaskets.
15. Beginning with th e bur ner r emoved in s tep

13, reinstall all the components in the reverse

order that they were removed.

16. Make s ure to ali gn th e bu rner hous ing with

the blower and the heat exchanger top head.

17. Check to ens ure that t he grounding screw is

reinstalled. Also, ens ure that c onductive,

high-temperature, a nti-seize c ompound is

applied to th e thr eads of the gr ound s crew

and th e ig nitor-injector. T orque th e ig nitor-

injector t o 8 0 t o 9 0 in-lbs. H owever, if t he

burner housing w as r eplaced during

inspection, tor que to 18 0 i n-lbs, then l oosen

and re-tighten to 80 to 90 in-lbs.

IGNITOR-

INJECTOR

FLAME

DETECTOR

STAGED IGNITION

ASSEMBLY

BURNER GASKET

BURNER

BURNER GASKET

BURNER

HOUSING

Figure 7-4

Burner Assembly - Exploded View

7.7 CONDENSATE DRAIN TRAPS

The Benc hmark 3.0 B

oiler c ontains t wo

condensate traps as shown in Chapter 2, Figure

2-5. One trap is located external to t he unit and

attached to the drain p ipe f rom the c onnecting

manifold. The other trap is an integral part of the

exhaust m anifold. T hese tr aps s hould b e

inspected an d, if nec essary, c leaned t o ens ure

proper o peration. F ollow the pr ocedures i n

paragraphs 7.7.1 and 7.7.2.

7.7.1 Connecting Manifold Condensate
Trap

To ins pect an d c lean t he condensate tr ap ( part

no. 24060) attached to the connecting manifold,

proceed as follows:

1. Loosen th e t humbscrew securing the tr ap

adaptor (Figure 2-6) to th e condensate drain

pipe on the connecting manifold.

2. Remove the n ipples and c onnections on the

inlet and out let sides of the condensate trap

shown in Figure 7-5.

7-4