Installation – AERCO BMK 3.0 LN Nat. Gas Jan 2011 User Manual

Page 22

Advertising
background image

INSTALLATION

2-10

22 AWG, s uch as Bel den 9 841 ( see

Figure 2-11). Polarity must be m aintained. T he

shield must be connected only at the source end

and m ust be left floating ( not connected) at the

Boiler’s I/O Box.

Regardless of whether voltage or current is used

for the dr ive signal, they are linearly mapped to

a 40°F to 240°F setpoint or a 0% to 100% f iring

rate. No scaling for these signals is provided

2.10.4 B.M.S. (PWM) IN

NOTE

Only BMS Mod el 1 68 c an uti lize P ulse

Width Modulation (PWM), not the BMS II

(Model 5R5-384).

These ter minals ar e used t o c onnect t he

AERCO Boi ler Ma nagement S ystem ( BMS)

Model 16 8 to the un it. T he BMS Mod el 1 68

utilizes a 12 m illisecond, ON/OFF dut y c ycle.

This duty cycle is Pulse Width Modulated (PWM)

to control firing rate. A 0% firing rate = a 5% ON

pulse and a 100% firing rate = a 95% ON pulse.

2.10.5 SHIELD

The SHIELD terminals are used to terminate any

shields us ed on s ensor wires c onnected to t he

unit. O nly s hields m ust be c onnected t o th ese

terminals.

IMPORTANT

DO NO T USE the m A OUT output to

remotely monitor Setpoint, Outlet Temp or

Fire Rate Out.

2.10.6 mA OUT

These terminals provide a 4 to 20 m A output to

the VFD (if so equipped) to control the rotational

speed of the blower. This function is enabled in

the Configuration Menu (Chapter 3, Table 3-4).

2.10.7 0 – 10V OUT

These ter minals pr ovide a 0 to 10V o utput to

control t he r otational s peed of the b lower. T his

function is e nabled i n t he Conf iguration Me nu

(Chapter 3, Table 3-4).

2.10.8 RS-485 COMM

These terminals are used for RS-485 MODBUS

serial c ommunication be tween the u nit a nd an

external “Master” such as a Boiler Management

System ( BMS), En ergy Management S ystem

(EMS), Building Automation S ystem ( BAS) or

other suitable device.

2.10.9 EXHAUST SWITCH IN

These ter minals per mit an ex ternal ex haust

switch to be c onnected to the exhaust m anifold

of the bo iler. T he ex haust s witch s hould be a

normally open type switch (such as AERCO Part

No. 123463) that closes (trips) at 500°F.

2.10.10 INTERLOCKS

The unit

offers tw o i nterlock c ircuits f or

interfacing with En ergy M anagement Systems

and a uxiliary eq uipment s uch as pum ps or

louvers. These interlocks are called the Remote

Interlock and Dela yed I nterlock ( Figure 2- 11).

The w iring ter minals f or these int erlocks ar e

located i nside th e I/O Box on t he u nit f ront

panel. T he I/O Box c over c ontains a wiring

diagram which shows the terminal strip locations

for thes e inter locks ( REMOTE IN TL’K IN and

DELAYED INT L’K IN). Both

interlocks,

described below, are factory wired in the c losed

position.

IMPORTANT

Both th e Rem ote In terlock and Del ayed

Interlock MUST be in the c losed pos ition

to allow the unit to fire.

2.10.10.1 REMOTE INTERLOCK IN

The r emote inter lock c ircuit is pr ovided to

remotely s tart ( enable) an d s top ( disable) th e

Boiler, if des ired. T he c ircuit is labe led

REMOTE INTL’K IN and is located inside the I/O

Box on t he f ront pan el. T he c ircuit is 24 V AC

and is factory pre-wired in the closed (jumpered)

position.

2.10.10.2 DELAYED INTERLOCK IN

The del ayed interlock is t ypically used i n

conjunction with t he aux iliary r elay described in

paragraph 2. 10. T his inter lock c ircuit is loc ated

in the purge section of the start string. It c an be

connected to t he proving dev ice ( end s witch,

flow s witch etc .) of an aux iliary p iece of

equipment started by the Boiler’s auxiliary relay.

The dela yed i nterlock must be c losed f or the

boiler to fire.

If the delayed interlock is connected to a proving

device that requires time to close (make), a time

delay ( Aux Start O n D ly) that ho lds t he s tart

sequence of the boiler long enough for a proving

switch to make can be programmed. Should the

proving switch not prove within the programmed

time fr ame, the bo iler wi ll shut do wn. T he Aux

Start On Dly can be programmed from 0 to 120

seconds. T

his option is l ocate i n t he

Configuration Menu (Chapter 3, Table 3-4).

Advertising