TROUBLESHOOTING

TABLE 8-1. BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

(continued)

2. Defective or shorted switch.

3. Switch wired incorrectly.
4. Defective Power Supply Board or

fuse

5. Defective IGST Board

2. If the Air/Fuel Valve does rotate to the ignition position, check the

purge switch for continuity between the N.O. and COM terminals.

If the switch shows continuity when not in c ontact with the c am,

check to ens ure that the s witch is wired correctly (correct wire

numbers on the normally open terminals).

3. If the switch is wired correctly, replace the switch.
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not

steady ON, replace Power Supply Board.

5. Check “Heartbeat” LED DS1 and ver ify it is blinking ON & O FF

every second. If not, replace IGST Board.

PRG SWTCH OPEN

DURING PURGE

1. Defective purge switch.

2. No voltage present at switch.

3. Switch wired incorrectly.

4. Defective Power Supply Board or

fuse

5. Defective IGST Board

1. If the air -fuel valve does r otate, c heck the purge switch for

continuity w hen c losing. Replac e s witch if c ontinuity does not

exist.

2. Measure for 24 VAC f rom each side of the s witch to gr ound. If

24VAC is not present, refer fault to qualified service personnel.

3. Check to ens ure that the s witch is w ired c orrectly (correct wire

numbers on the normally open terminals).

4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not

steady ON, replace Power Supply Board.

5. Check “Heartbeat” LED DS1 and ver ify it is blinking ON & O FF

every second. If not, replace IGST Board.

OUTDOOR TEMP

SENSOR FAULT

1. Loose or broken wiring.
2. Defective Sensor.

3. Incorrect Sensor.

1. Inspect Outdoor Temperature sensor for loose or broken wiring.
2. Check resistance of sensor to determine if it is within

specification.

3. Ensure that the correct sensor is installed.

REMOTE SETPT

SIGNAL FAULT

1. Remote setpoint signal not present:

Not yet installed.

Wrong polarity.

Signal defective at source.

Broken or loose wiring.

2. Signal is not isolated (floating) if 4 to

20 mA.

3. Control Box signal type selection

switches not set for correct signal

type (voltage or current).

1. Check I/O Box to ensure signal is hooked up.

Hook up if not installed.

If installed, check polarity.

Measure signal level.

Check continuity of wiring between source and boiler.

2. Check signal at source to ensure it is isolated.

3. Check DIP switch on PMC board to ensure it is set correctly for

the type of signal being sent. Check control signal type set in

Configuration Menu.