Installation – AERCO BMK 3.0 LN Nat. Gas Jan 2011 User Manual

Page 24

Advertising
background image

INSTALLATION

2-12

2.13.2 Combustion Air From Inside the
Building

When combustion air is provided from within the

building, it m ust be s upplied thr ough t wo

permanent op enings i n a n int erior wall. Each

opening must have a free area of not less than

one square inch per 1000 BTU/H of total boiler

input. The free area must take into account any

restrictions such as louvers.

2.13.3 Sealed Combustion

The AER CO Benchmark 3.0 Boiler is U L listed

for 100%- sealed c ombustion. F or s ealed

combustion ins tallations, t he s creen on the a ir

inlet duct of the unit must be removed. The inlet

air duc twork must then be attac hed dir ectly t o

the unit’s air inlet.

In a s ealed c ombustion air app lication, the

combustion air ducting pressure losses must be

taken into ac count when c alculating th e tota l

maximum allo wable v enting r un. See t he

AERCO Be nchmark Venti ng an d Com bustion

Air Guide, GF-2050. When using the boiler in a

sealed c ombustion a ir c onfiguration, each unit

must have a m

inimum 8- inch diam eter

connection at the unit.

2.13.4 Temporary Combustion Air
Filtering During Construction

When the AERCO Benchmark 3.0 Boiler is used

to pr ovide he at tem porarily dur ing ongoing

building construction, accumulated drywall dust,

sawdust and similar particles can accumulate in

the un it’s c ombustion a ir i ntake f ilter and b lock

combustion air flow. In these situations, AERCO

recommends that a disposable air intake filter be

installed, temporarily, abo ve the bo

iler

combustion air inlet.

AERCO recommends that the temporary air filter

be cut from a McMaster-Carr part no. 2122K315

Polyester Air Filter Roll Tackfield, 1/2” thick, 16”

wide, or e quivalent. C over the Benchmark 3.0

air in let with the b lue s ide of the f ilter m aterial

facing out ward to hold th e dus t on t he o utside

surface. Max imize th e s urface ar ea of the f ilter

covering the 8 " di ameter opening b y c reating a

dome out of the filter material.

During c onstruction, c heck the f ilter f or dus t

accumulation a nd r eplace it

when t he

accumulation becomes noticeable.

Advertising