INITIAL START-UP

37. Press the

▼ arrow key until CAL Voltage

40%

is displayed.

38. Press the CHANGE key. CAL Voltage 40%

will begin to flash.

39. The oxygen level at the 40% valve position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

40% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

7.8 %

<50 ppm

<20 ppm

40. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.

41. Once the oxygen level is within the specified

range at 40%, press the ENTER key to store
the selected blower output voltage for the
40% valve position.

42. Press the ▲ arrow key until SET Valve

Position

appears on the C-MORE display.

43. Press the CHANGE key. SET Valve Position

will begin to flash.

44. Press the ▼ arrow key until the SET Valve

Position

reads 30%, then press the ENTER

key.

45. Press the

▼ arrow key until CAL Voltage

30%

is displayed.

46. Press the CHANGE key. CAL Voltage 30%

will begin to flash.

47. The oxygen level at the 30% Valve Position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

30% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

8.0 %

<50 ppm

<20 ppm

48. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼

arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.

49. Once the oxygen level is within the specified

range at 30%, press the ENTER key to store
the selected blower output voltage for the
30% valve position.

50. Press the ▲ arrow key until SET Valve

Position

appears on the C-MORE display.

51. Press the CHANGE key. SET Valve Position

will begin to flash.

52. Press the ▼ arrow key until the SET Valve

Position

reads 14%, then press the ENTER

key.

53. Press the

▼ arrow key until CAL Voltage

14%

is displayed.

54. Press the CHANGE key. CAL Voltage 14%

will begin to flash.

55. The oxygen level at the 14% Valve Position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

14% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

8.5 %

<50 ppm

<30 ppm

56. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
▼ arrow key decreases the oxygen level.

57. Once the oxygen level is within the specified

range at 14%, press the ENTER key to store
the selected blower output voltage for 14%
Valve Position.

IMPORTANT

Repeat steps 18 through 57 until the
blower output voltage does not require
adjustment when sequencing from 70% to
14%.

58. This completes the natural gas combustion

calibration procedure.