MAINTENANCE

CHAPTER 7 MAINTENANCE

7.1 MAINTENANCE SCHEDULE

The unit requires regular routine maintenance to

keep up efficiency a nd r eliability. F or bes t

operation and l ife of the unit, th

e f ollowing

routine m aintenance procedures s hould be

carried out in the time periods specified in Table

7-1. S ee A ppendix I f or a c omplete CSD- 1

inspection check list.

In or der to perform the m aintenance tas ks

specified i n T able 7 -1, the f

ollowing

maintenance k its ar e av ailable thr ough your

local AERCO Sales Representative:

Annual Maintenance Kit, Part No. 58025-01

24- Month Waterside/Fireside Inspection Kit,

Part No. 58025-04 (See NOTE below)

NOTE

The 24-Month Waterside/Fireside Inspec-

tion Kit also includes the items contained

in the Annual Maintenance Kit. T herefore,

only Kit Par t No. 5 8025-04 is r equired

when per forming the w aterside/fireside

inspections.

Appendix K c ontains recommended spare parts

lists for maintenance of the boiler.

WARNING

TO A VOID P ERSONAL IN JURY,

PRIOR TO SERVICING:

DISCONNECT THE AC SUPPLY BY

TURNING O FF THE SERVI CE

SWITCH AND AC SUP PLY CIRCUIT

BREAKER.

SHUT O FF THE G AS SUPPLY AT

THE M ANUAL SHUT -OFF VALVE

PROVIDED WITH THE UNIT

ALLOW T HE UNIT TO C OOL T O A

SAFE WATER T EMPERATURE T O

PREVENT BURNING OR SCALDING




7.2 IGNITOR-INJECTOR

The ignitor-injector (part no. 58023) is located in

the bo dy of the b urner (see F igure 7- 1). In

addition t o pr oviding t he ignition s park r equired

to light the bur ner, this component also contains

a gas injector tube which connects to the staged

ignition as sembly. T he ig nitor-injector m ay be

hot, therefore, care should be exercised to avoid

burns. It is eas ier t o r emove the i gnitor-injector

from the uni t af ter th e u nit has c ooled to r oom

temperature.

BURNER

HOUSING

FLAME DETECTOR

& GASKET (SECURED

WITH 2 SCREWS)

IGNITOR-

INJECTOR

STAGED

IGNITION

ASSY

Figure 7-1.

Burner Assembly – Top View

To ins pect/replace th e Ign itor-injector, pr oceed

as follows:

1. Set the ON/OFF switch on the c ontrol panel,

to the OFF pos ition. Dis connect AC p ower

from the unit

2. Remove th e t op and s ide pan els f rom the

unit.

3. Disconnect the cable from the ignitor-injector.

4. Using a 7/ 16” ope n-end wr ench, dis connect

the compression nut securing the gas injector

tube of the ignitor-injector to the el bow of the

staged i gnition as sembly. Dis connect the

staged ig nition as sembly f rom the ig nitor-

injector.

7-1